HomeMy WebLinkAboutOrdinance No. 2663-2012/ .. Suggested by: Administration
ekeL1'ry� CITY OF KENAI
KEN � SKii
ORDINANCE NO. 2663-2012
AN ORDINANCE OF THE COUNCIL OF THE CITY OF KENAI, ALASKA, AMENDING
CHAPTER 4.20, MECHANICAL CODE, BY ADOPTING THE 2009 EDITION OF THE
INTERNATIONAL MECHANICAL CODE AND MAKING LOCAL AMENDMENTS.
WHEREAS, the City previously adopted the International Mechanical Code, 2006
Edition, of the International Code Council, including the appendices with certain local
amendments; and,
WHEREAS, the International Code Council updated the International Mechanical Code
in 2009; and,
WHEREAS, the City's Building Official accordingly recommends adoption of the 2009
Edition of the International Mechanical Code, with certain amendments; and,
WHEREAS, it is in the best interest of the City to adopt the 2009 Edition of the
International Mechanical Code and the updated standards therein, as amended for the
City, in order to protect the health, safety, and welfare of its citizens.
NOW, THEREFORE, BE IT ORDAINED BY THE COUNCIL OF THE CITY OF KENAI,
ALASKA, as follows:
Section 1. Form: This is a Code ordinance.
Section 2. Amendment of Chanter 4.20 of the Kenai Municipal Code: The Kenai
Municipal Code, Chapter 4.20, Mechanical Code, is hereby amended as follows:
Chapter 4.20
MECHANICAL CODE
4.20.010 Adoption.
4.20.015 Local amendments to the 200[6]9 International Mechanical Code.
4.20.020 Building Official.
4.20.030 Fee schedule.
4.20.010 Adoption.
There is hereby adopted for the purpose of establishing rules and regulations
for the installation and maintenance of heating, ventilating, cooling, and refrigeration
systems, that certain code known as the "International Mechanical Code," 200[6]9
Edition, of the International Code Council, including the appendices, except for such
portions as are hereafter deleted, modified, or amended; and the same is hereby
adopted and incorporated as fully as if set out verbatim herein.
Ordinance No. 2663-2012
Page 2 of 21
4.20.015 Local amendments to the 200[6]9 International Mechanical Code.
[THE INTERNATIONAL MECHANICAL CODE (I.M.C.) CHAPTERS 1-15 AND
APPENDIX A (2006 EDITION) ARE ADOPTED BY REFERENCE TO REGULATE ALL
OCCUPANCIES AND BUILDINGS WITH THE FOLLOWING REVISIONS:
SECTION 109 MEANS OF APPEAL.
DELETE ENTIRE SECTION. REFER TO CHAPTER 4.40 OF KMC.
201.3 TERMS DEFINED IN OTHER CODES.
REVISE BY DELETING THE REFERENCE "ICC ELECTRICAL CODE" AND
REPLACE WITH THE REFERENCE "ELECTRICAL CODE AS ADOPTED BY KMC."
REVISE BY DELETING THE REFERENCE "INTERNATIONAL PLUMBING CODE"
AND INSERTING THE REFERENCE "PLUMBING CODE AS ADOPTED BY KMC."
202 GENERAL DEFINITIONS.
AMEND BY ADDING THE FOLLOWING DEFINITIONS:
HEAT RECOVERY DEVICE. AN ASSEMBLY CONTAINING A HEAT RECOVERY
ELEMENT.
HEAT RECOVERY ELEMENT. A DEVICE OR SERIES OF DEVICES WHOSE PURPOSE
IS TO RECLAIM ONLY THE HEAT CONTENT OF AIR, VAPORS, GASES, AND/OR
FLUIDS THAT WERE BEING EXPELLED THROUGH THE EXHAUST SYSTEM, AND
TRANSFERRING THE THERMAL ENERGY SO RECLAIMED TO A LOCATION
WHEREBY A USEFUL PURPOSE MAY BE SERVED.
301.2 ENERGY UTILIZATION.
REVISE BY DELETING THE WORDS "IN ACCORDANCE WITH THE
INTERNATIONAL ENERGY CONSERVATION CODE."
301.7 ELECTRICAL.
REVISE BY DELETING THE REFERENCE TO "ICC ELECTRICAL CODE" AND
INSERTING THE REFERENCE "ELECTRICAL CODE AS ADOPTED BY KMC."
301.8 PLUMBING
REVISE BY DELETING THE REFERENCE "INTERNATIONAL PLUMBING CODE"
AND INSERTING THE REFERENCE "PLUMBING CODE AS ADOPTED BY THE KMC."
303.3 PROHIBITED LOCATIONS.
New Text. Underlined; [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 3 of 21
FROM THE THIRD EXCEPTION, DELETE THE WORDS "WEATHER STRIPPED
IN ACCORDANCE WITH THE EXTERIOR DOOR AIR LEAKAGE REQUIREMENTS OF
THE INTERNATIONAL ENERGY CONSERVATION CODE AND."
INSERT THE WORDS "TIGHTLY GASKETED" BEFORE "SOLID" TO READ
"TIGHTLY GASKETED SOLID DOOR."
303.8 ELEVATOR SHAFTS.
AMEND SENTENCE TO READ AS FOLLOWS:
MECHANICAL SYSTEMS SHALL NOT BE LOCATED IN AN ELEVATOR SHAFT
WITH THE EXCEPTION OF MECHANICAL EQUIPMENT AND DEVICES EXCLUSIVELY
SERVING THE ELEVATOR.
304.8 CLEARANCES TO COMBUSTIBLE CONSTRUCTION.
REVISE TO READ AS FOLLOWS:
HEAT PRODUCING EQUIPMENT AND APPLIANCES SHALL BE INSTALLED TO
MAINTAIN THE REQUIRED CLEARANCES TO COMBUSTIBLE CONSTRUCTION AS
SPECIFIED IN THE LISTING AND MANUFACTURERS INSTRUCTIONS. SUCH
CLEARANCES SHALL BE REDUCED ONLY IN ACCORDANCE WITH SECTION 308.
CERTAIN UNLISTED HEAT -PRODUCING EQUIPMENT SHALL BE ALLOWED
PROVIDED IT IS INSTALLED IN A MANNER SO AS TO MAINTAIN THE CLEARANCES
TO COMBUSTIBLE CONSTRUCTION SPECIFIED IN TABLE 304.8. CLEARANCES TO
COMBUSTIBLES SHALL INCLUDE SUCH CONSIDERATIONS AS DOOR SWING,
DRAWER PULL, OVERHEAD PROJECTIONS, OR SHELVING AND WINDOW SWING,
SHUTTERS, COVERINGS, AND DRAPES. DEVICES SUCH AS DOORSTOPS OR
LIMITS, CLOSERS, DRAPERY TIES OR GUARDS SHALL NOT BE USED TO PROVIDE
THE REQUIRED CLEARANCES.
New Text Underlined; [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 4 of 21
REVISE BY ADDING TABLE 304.8 AND TABLE 304.8.1 AS FOLLOWS:
TABLE 304.8
STANDARD INSTALLATION CLEARANCES IN INCHES FOR
CERTAIN UNLISTED HEAT PRODUCING APPLIANCES
New Text Underlined; [DELETED TEXT BRACKETED]
FROM TOP
ABOVE
AND SIDES OF
TOP OF
WARM -AIR
CASING OR
BONNET OR
FROM
FROM
FROM
APPLIANCES
FUEL
APPLIANCE
PLENUM
FRONT'
BACK6
SIDES6
RESIDENTIAL TYPE
FURNACES—FLOOR
SOLID
182
182
48
18
18
AUTOMATIC
FOR MOUNTING ON
COMBUSTIBLE
OIL OR
COMB.
FLOORS.
GAS -OIL
36
12
12
12
ROOM HEATERS'
CIRCULATING TYPE
OIL OR
SOLID
36
24
12
12
RADIANT OR OTHER TYPE
OIL OR
SOLID
36
36
36
36
FIREPLACE STOVE
SOLID
484
5°
48°
484
INCINERATORS
DOMESTIC TYPES
365
48
36
36
COMMERCIAL — TYPE
LOW HEAT APPLIANCES
UNIT HEATERS
FLOOR MOUNT ANY SIZE
ALL FUELS
18
48
18
18
OTHER LOW -HEAT
INDUSTRIAL APPLIANCES.
FLOOR -MOUNTED OR
SUSPENDED
ALLFUELS
18
18
48
18
18
COMMERCIAL INDUSTRIAL —
TYPE
MEDIUM HEAT APPLIANCES
INCINERATORS
ALL SIZES
48
96
36
36
New Text Underlined; [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 5 of 21
FOOTNOTES:
'THE MINIMUM DIMENSION SHALL BE THAT NECESSARY FOR SERVICING THE APPLIANCE, INCLUDING
ACCESS FOR CLEANING AND NORMAL CARE, TUBE REMOVAL, ETC.
2THE DIMENSION MAY BE 6 INCHES (152 MM) FOR AN AUTOMATICALLY STOKER -FIRED FORCED -WARM -AIR
FURNACE EQUIPPED WITH 250 DEGREE FAHRENHEIT LIMIT CONTROL AND WITH BAROMETRIC DRAFT
CONTROL OPERATED BY DRAFT INTENSITY AND PERMANENTLY SET TO LIMIT DRAFT TO A MAXIMUM
INTENSITY OF 0.13 -INCH WATER GAUGE (32PA).
'APPROVED APPLIANCES SHALL BE INSTALLED ON NON-COMBUSTIBLE FLOORS AND MAY BE INSTALLED
ON PROTECTED COMBUSTIBLE FLOORS. HEATING APPLIANCES APPROVED FOR INSTALLATION ON
PROTECTED COMBUSTIBLE FLOORING SHALL BE SO CONSTRUCTED THAT FLAME AND HOT GASES DO NOT
COME IN CONTACT WITH THE APPLIANCE BASE. PROTECTION FOR COMBUSTIBLE FLOORS SHALL CONSIST
OF 4 -INCH (102 MM) HOLLOW MASONRY COVERED WITH SHEET METAL AT LEAST 0.021 INCH (0.5 MM)
THICK (NO. 24 MANUFACTURER'S STANDARD GAUGE). MASONRY SHALL BE PERMANENTLY FASTENED IN
PLACE IN AN APPROVED MANNER WITH THE ENDS UNSEALED AND JOINTS MATCHED SO AS TO PROVIDE
FREE CIRCULATION OF AIR THROUGH THE MASONRY. FLOOR PROTECTION SHALL EXTEND 12 INCHES (305
MM) AT THE SIDES AND REAR OF THE APPLIANCE, EXCEPT THAT AT LEAST 18 INCHES (457 MM) SHALL BE
REQUIRED ON THE APPLIANCE -OPENING SIDE OR SIDES MEASURED HORIZONTALLY FROM THE EDGES OF
THE OPENING.
"THE 48 -INCH (1219 MM) CLEARANCE MAY BE REDUCED TO 36 INCHES (914 MM) WHEN PROTECTION
EQUIVALENT TO THAT PROVIDED BY ITEMS I THROUGH 6 OF TABLE 304.8.1 IS APPLIED TO THE
COMBUSTIBLE CONSTRUCTION.
5CLEARANCE ABOVE THE CHARGING DOOR MUST BE AT LEAST 48 INCHES (1219 MM).
6 I THE APPLIANCE IS ENCASED IN BRICK THE 18 -INCH (457 MM) CLEARANCE ABOVE AND AT SIDES AND
REAR MAY BE REDUCED TO 12 INCHES (305 MM).
TABLE 304.8.1
CLEARANCES, IN INCHES, WITH SPECIFIED FORMS OF PROTECTION'2
TYPE OF
WHERE THE STANDARD CLEARANCE IN TABLE 304.8 WITH NO PROTECTION IS:
PROTECTI
ON
36 INCHES
18 INCHES
12 INCHES
6INCHES
APPLIED TO
THE
COMBUSTIB
LE
MATERIAL
UNLESS
OTHERWISE
SPECIFIED
AND
COVERING
ALL
X25.4 MM
SURFACES
WITHIN THE
DISTANCE
SPECIFIED
ASTHE
REQUIRED
CLEARANC
E WITH NO
PROTECTIO
N
X 25.4 FORABO
CHIMNE
ABO
CHIMNE
ABO
ABO
CHIMNE
MM
VE
SID
Y OR
VE
SID
Y OR
VE
SID
CHIMNE
VE
SID
Y OR
New Text Underlined; [DELETED TEXT BRACKETED.)
Ordinance No. 2663-2012
Page 6 of 21
New Test Underlined; [DELETED TEXT BRACKETED] ---
- - - - - -
ES
VENT
ES
VENT
ES
Y
ES
VENT
CONNEC
CONNEC
CONNEC
AN
TION
AN
TION
AN
OR
AN
TION
D
D
D
VENT
D
CONNEC
RE
RE
RE
TION
RE
AR
AR
AR
AR
1.1/4"
30
18
30
15
9
12
9
6
6
3
2
3
INSULATIN
G MILL
BOARD
SPACED
OUT Ire
2.0.013"
24
18
24
12
9
12
9
6
4
3
2
2
(NO. 28
MANUFACT
URER'S
STANDARD
GAUGE)
STEEL
SHEET ON
1/4"
INSULATIN
G MILL
BOARD
3.0.013"
18
12
18
9
6
9
6
4
4
2
2
2
(NO. 28
MANUFACT
URER'S
STANDARD
GAUGE)
STEEL
SHEET
SPACED
OUT r"
4.0.013"
18
12
18
9
6
9
6
4
4
2
2
2
(NO. 28
MANUFACT
URER'S
STANDARD
GAUGE)
STEEL
SHEET ON
1/8"
INSULATIN
G MILL
BOARD
SPACED
OUT 1,3
5.11/2"
18
12
36
9
6
18
6
4
9
2
1
6
INSULATIN
G CEMENT
COVERING
ON
HEATING
APPLIANCE
18
12
18
6
6
6
4
4
4
2
2
2
New Test Underlined; [DELETED TEXT BRACKETED] ---
- - - - - -
Ordinance No. 2663-2012
Page 7 of 21
INSULATIN
G MILL
BOARD ON
I" MINERAL
FIBER
BATTS
REINFORCE
D WITH
WIRE MESH
OR
EQUIVALEN
T
'FOR APPLIANCES COMPLYING WITH SECTIONS 304.2 AND 304.3.
EXCEPT FOR THE PROTECTION DESCRIBED IN ITEM 5, ALL CLEARANCES SHALL BE MEASURED FROM THE OUTER
SURFACE OF THE APPLIANCE TO THE COMBUSTIBLE MATERIAL, DISREGARDING ANY INTERVENING PROTECTION
APPLIED TO THE COMBUSTIBLE MATERIAL.
'SPACERS SHALL BE OF NONCOMBUSTIBLE MATERIAL.
NOTE: INSULATING MILLBOARD IS FACTORY -MADE PRODUCT FORMED OF NONCOMBUSTIBLE MATERIALS, NORMALLY
FIBERS, AND HAVING A THERMAL CONDUCTIVITY OF I BTU -INCH PER SQUARE FOOT PER DEGREE FAHRENHEIT OR LESS.
312.1 LOAD CALCULATIONS.
REVISE THE THIRD SENTENCE BY DELETING THE WORDS "USING THE
DESIGN PARAMETERS SPECIFIED IN CHAPTER 3 OF THE INTERNATIONAL ENERGY
CONSERVATION CODE."
403.3 VENTILATION RATE.
AMEND BY ADDING TO THE END OF THE FIRST SENTENCE THE WORDS
"OR IN ACCORDANCE WITH THE LATEST VERSION OF ASHRAE STANDARD 62."
513 SMOKE CONTROL SYSTEMS.
REVISE BY DELETING THE REFERENCE "ICC ELECTRICAL CODE" AND
REPLACING IT WITH THE REFERENCE "ELECTRICAL CODE AS ADOPTED BY KMC
WHEREVER IT OCCURS IN THIS SECTION."
514.1 GENERAL.
DELETE THE SECOND SENTENCE AND REPLACE WITH "ENERGY RECOVERY
VENTILATION SYSTEMS MUST BE INSTALLED ACCORDING TO THE
MANUFACTURER'S INSTRUCTIONS AND SPECIFICATIONS.
601.4 CONTAMINATION PREVENTION.
AMEND BY ADDING THE FOLLOWING EXCEPTION TO 601.4 TO READ AS
FOLLOWS:
_. New Text Underlined; [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 8 of 21
�^ EXCEPTION: ENVIRONMENTAL AIR EXHAUST DUCTS UNDER POSITIVE
PRESSURE MAY EXTEND INTO OR THROUGH DUCTS OR PLENUMS IF ONE OF THE
FOLLOWING DESIGN APPROACHES IS USED:
ROUTE ENVIRONMENTAL AIR EXHAUST DUCTS INSIDE A SHAFT
WHEN PASSING THROUGH A DUCT OR PLENUM.
2. INSTALL A SECOND DUCT AROUND THE ENVIRONMENTAL AIR
EXHAUST DUCT WHERE PASSING THROUGH DUCTS AND PLENUMS
TO MINIMIZE LEAKAGE TO THE DUCT OR PLENUM. SEAL BOTH ENDS
OF THE OUTER DUCT TO OUTSIDE.
SEAL THE ENVIRONMENTAL AIR EXHAUST DUCTS ALONG ALL SEAMS
AND JOINTS USING A LISTED LOW TO MEDIUM PRESSURE DUCT
SEALANT WHICH IS TYPICALLY APPLIED BY BRUSH, TROWEL OR
CAULKING GUN. INSTALL SEALANT PER MANUFACTURER'S
RECOMMENDATIONS.
4. PROVIDE FLEXIBLE DUCT WITH NO SEAMS IN THE DUCT OR PLENUM
ONLY TO A LIMIT OF 8'. THE 8' LIMIT IS DUE TO HIGH STATIC
LOSSES. ALSO, SLEEVING THE METAL DUCT WITH FLEXIBLE
SEAMLESS DUCT IS ACCEPTABLE.
602.1 GENERAL.
DELETE FROM THE SECOND SENTENCE THE WORDS "UNINHABITED
CRAWL SPACES."
ADD THE FOLLOWING SENTENCE TO THE END OF THE PARAGRAPH:
"UNDERFLOOR CRAWLSPACES SHALL NOT BE USED AS PLENUMS."
603.9 JOINTS, SEAMS, AND
DELETE PARAGRAPH AND REPLACE WITH THE FOLLOWING:
ALL JOINTS, LONGITUDINAL AND TRANSVERSE SEAMS, AND CONNECTIONS
IN DUCTWORK, SHALL BE SECURELY FASTENED AND SEALED WITH WELDS,
GASKETS, MASTICS (ADHESIVES), MASTIC -PLUS -EMBEDDED -FABRIC SYSTEMS
OR TAPES. TAPES AND MASTICS USED TO SEAL DUCTWORK SHALL BE LISTED
AND LABELED IN ACCORDANCE WITH UL 181A OR UL 181B DUCT CONNECTIONS
TO FLANGES OF AIR DISTRIBUTION SYSTEM EQUIPMENT SHALL BE SEALED AND
MECHANICALLY FASTENED. DUCT TAPE IS NOT PERMITTED AS A SEALANT ON
ANY METAL DUCTS.
ADD THE FOLLOWING EXCEPTION:
New Text Underlined; ]DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 9 of 21
EXCEPTION: CONTINUOUSLY WELDED AND LOCKING -TYPE LONGITUDINAL
JOINTS AND SEAMS ON DUCTS OPERATING AT STATIC PRESSURES LESS THAN 2
INCHES W.G. (500 PA) PRESSURE CLASSIFICATION.
604.1 GENERAL.
DELETE THE WORDS "AND THE INTERNATIONAL ENERGY CONSERVATION
CODE."
ADD TO THE END OF THE PARAGRAPH:
ALL SUPPLY AND RETURN AIR DUCTS AND PLENUMS SHALL BE INSULATED
WITH A MINIMUM OF R-5 INSULATION WHEN LOCATED IN UNCONDITIONED
SPACES AND WITH A MINIMUM OF R-8 INSULATION WHEN LOCATED OUTSIDE
THE BUILDING ENVELOPE. WHEN LOCATED WITHIN A BUILDING ENVELOPE
ASSEMBLY, THE DUCT OR PLENUM SHALL BE SEPARATED FROM THE BUILDING
EXTERIOR OR UNCONDITIONED OR EXEMPT SPACES BY A MINIMUM OF R-8
INSULATION.
EXCEPTIONS:
1. WHEN LOCATED WITHIN EQUIPMENT.
2. WHEN THE DESIGN TEMPERATURE DIFFERENCE BETWEEN THE
INTERIOR AND EXTERIOR OF THE DUCT OR PLENUM DOES NOT
EXCEED 15°F (8°C).
3. WHEN LOCATED WITHIN THE UNDER FLOOR CRAWLSPACE OF A
ONE- OR TWO-FAMILY DWELLING UNIT.
709.1 GENERAL.
REVISE BY ADDING A SECOND SENTENCE TO READ:
COMBUSTION -AIR OPENINGS MUST BE COVERED WITH CORROSION -
RESISTANT SCREEN OF NO GREATER THAN 1 -INCH (13 MM) MESH.
801.21 LOCATIONS AND SUPPORT OF VENTING SYSTEMS OTHER THAN
MASONRY CHIMNEYS.
ADD A NEW SECTION 801.21 AS FOLLOWS:
UNLESS A VENT LISTED FOR EXTERIOR USE IN COLD WEATHER CLIMATES
IS INSTALLED, A VENTING SYSTEM INSTALLED EXTERIOR TO THE BUILDING
OUTSIDE THE THERMAL ENVELOPE SHALL BE INSTALLED IN A SHAFT. THE
PORTION OF THE VENT SYSTEM THAT IS ABOVE THE LAST ROOF .AND ITS
New Text Underlined; [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 10 of 21
PROJECTED PLANE NEED NOT BE ENCLOSED. THE PORTION OF THE VENTING
SYSTEM PASSING THROUGH AN ATTIC SPACE NEED NOT BE ENCLOSED.
908.5 WATER SUPPLY.
REVISE BY DELETING THE REFERENCE "INTERNATIONAL PLUMBING CODE"
AND INSERTING THE REFERENCE "PLUMBING CODE AS ADOPTED BY KMC."
SECTION 927 UNVENTED ROOM HEATERS.
REVISE BY ADDING A NEW SECTION 927 UNVENTED ROOM HEATERS TO
READ:
927.1 GENERAL. UNVENTED ROOM HEATERS SHALL BE TESTED IN
ACCORDANCE WITH AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) Z
21.11.2 AND MAY BE INSTALLED IN ACCORDANCE WITH THE CONDITIONS OF THE
LISTING AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
927.2 PROHIBITED USE. ONE OR MORE UNVENTED ROOM HEATERS MAY
NOT BE USED AS THE SOLE SOURCE OF COMFORT HEATING IN A DWELLING
UNIT.
927.3 INPUT RATING. UNVENTED ROOM HEATERS MAY NOT HAVE AN
INPUT RATING IN EXCESS OF 40,000 BTU/H (11.7 KW).
927.4 PROHIBITED LOCATIONS. UNVENTED ROOM HEATERS MAY NOT BE
INSTALLED WITHIN A, E OR I OCCUPANCIES. SUCH APPLIANCES MAY NOT BE
LOCATED IN OR OBTAIN COMBUSTION AIR FROM ANY OF THE FOLLOWING
ROOMS OR SPACES:
1. SLEEPING ROOMS.
2. BATHROOMS.
3. TOILET ROOMS.
4. STORAGE CLOSETS.
5. SURGICAL ROOMS.
EXCEPTIONS:
1. A SINGLE WALL -MOUNTED UNVENTED ROOM HEATER EQUIPPED
WITH AN OXYGEN DEPLETION SAFETY SHUTOFF SYSTEM AND
INSTALLED IN A BATHROOM PROVIDED THE INPUT RATING DOES
NOT EXCEED 6,000 BTU PER HOUR (1.76 KW) AND THE BATHROOM
IS NOT A CONFINED SPACE.
New Text Underlined; [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 11 of 21
2. A SINGLE WALL -MOUNTED UNVENTED ROOM HEATER EQUIPPED
WITH AN OXYGEN DEPLETION SAFETY SHUTOFF SYSTEM AND
INSTALLED IN A BEDROOM PROVIDED THAT THE INPUT RATING
DOES NOT EXCEED 10,000 BTU PER HOUR (2.93 KW) AND THE
BEDROOM IS NOT A CONFINED SPACE.
927.5 ROOM OR SPACE VOLUME.
THE AGGREGATE INPUT RATING OF ALL UNVENTED APPLIANCES
INSTALLED IN A ROOM OR SPACE MAY NOT EXCEED 20 BTU/H PER CUBIC FOOT
OF VOLUME OF SUCH ROOM OR SPACE. WHERE THE ROOM OR SPACE IN WHICH
THE EQUIPMENT IS INSTALLED IS DIRECTLY CONNECTED TO ANOTHER ROOM OR
SPACE BY A DOORWAY, ARCHWAY OR OTHER OPENING OF COMPARABLE SIZE
THAT CANNOT BE CLOSED, THE VOLUME OF SUCH ADJACENT ROOM OR SPACE
MAY BE PERMITTED TO BE INCLUDED IN THE CALCULATIONS.
927.6 OXYGEN -DEPLETION SAFETY SYSTEM.
UNVENTED ROOM HEATERS WILL BE EQUIPPED WITH AN OXYGEN -
DEPLETION -SENSITIVE SAFETY SHUTOFF SYSTEM. THE SYSTEM SHALL SHUT OFF
THE GAS SUPPLY TO THE MAIN AND PILOT BURNERS WHEN THE OXYGEN IN THE
SURROUNDING ATMOSPHERE IS DEPLETED TO THE PERCENT CONCENTRATION
SPECIFIED BY THE MANUFACTURER, BUT NOT LOWER THAN 18 PERCENT. THE
SYSTEM WILL NOT INCORPORATE FIELD ADJUSTMENT MEANS CAPABLE OF
CHANGING THE SET POINT AT WHICH THE SYSTEM ACTS TO SHUT OFF THE GAS
SUPPLY TO ROOM HEATER.
927.7 UNVENTED LOG HEATERS.
AN UNVENTED LOG HEATER MAY NOT BE INSTALLED IN A FACTORY -BUILT
FIREPLACE UNLESS THE FIREPLACE SYSTEM HAS BEEN SPECIFICALLY TESTED,
LISTED AND LABELED FOR SUCH USE IN ACCORDANCE WITH UNDERWRITERS
LABORATORIES (UL) 127.
CHAPTER 10 BOILERS, WATER HEATERS, AND PRESSURE VESSELS.
REVISE BY DELETING THE REFERENCES "INTERNATIONAL PLUMBING
CODE" AND INSERTING THE REFERENCES "PLUMBING CODE AS ADOPTED BY
KMC" WHEREVER THEY OCCUR IN THE CHAPTER.
1001.1 SCOPE.
REVISE TO READ:
THIS CHAPTER GOVERNS THE INSTALLATION, ALTERATION AND REPAIR OF
BOILERS, WATER HEATERS, AND PRESSURE VESSELS NOT SUBJECT TO THE
New Text Underlined; [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 12 of 21
PROVISIONS OF THE STATE DEPARTMENT OF LABOR UNDER AS 18.60.180
THROUGH 18.60.395.
1007.1 GENERAL.
REVISE BY DELETING THE WORDS "AND HOT WATER" FROM THE FIRST
SENTENCE.
SECTION 1011 TESTS.
DELETE THIS SECTION.
1101.4 WATER
REVISE BY DELETING THE REFERENCE "INTERNATIONAL PLUMBING CODE"
AND INSERTING THE REFERENCE "PLUMBING CODE AS ADOPTED BY KMC."
1201.1, 1206.2, AND 1206.3
REVISE BY DELETING THE
CODE" AND INSERTING THE REFE
KMC" WHEREVER THEY OCCUR.
;NCES "INTERNATIONAL PLUMBING
"PLUMBING CODE AS ADOPTED BY
1204.1 INSULATION CHARACTERISTICS.
REVISE THE FIRST SENTENCE BY DELETING THE WORDS "SHALL
CONFORM TO THE REQUIREMENTS OF THE INTERNATIONAL ENERGY
CONSERVATION CODE."
1204.2 REQUIRED THICKNESS.
REVISE BY DELETING THE WORDS "TO THE THICKNESS REQUIRED BY THE
INTERNATIONAL ENERGY CONSERVATION CODE."
1401.2 POTABLE WATER SUPPLY.
REVISE BY DELETING THE REFERENCE "INTERNATIONAL PLUMBING CODE"
AND INSERTING THE REFERENCE "PLUMBING CODE AS ADOPTED BY KMC."]
The International Mechanical Code (I.M.C.) Chapters 1-15 and Appendix A
(2009 Edition) are adopted by reference to regulate all occupancies and buildings with
the following revisions:
Delete all the references to the International Energy Conservation Code.
108.4 Violation penalties.
New Teat Underlined;.)DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 13 of 21
Delete the entire section. Refer to KMC Chapter 4.40.
109 Means of Appeal.
Delete the entire section. Refer to KMC Chapter 4.40.
201.3 Terms defined in other codes.
Amend by deleting the reference "ICC Electrical Code" and replace it with
"Electrical Code as adopted by KMC."
Amend by deleting the reference "International Plumbing Code" and replace it
with "Plumbing Code as adopted by KMC."
Amend by deleting the reference "International Peel Gas Code" and replace it
with "Uniform Plumbing Code as adopted by KMC."
301.2 Energy utilization.
Amend by deleting the phrase "in accordance with the International Energy
Conservation Code."
301.3 Fuel Gas Appliances and Equipment.
Amend by deleting the reference "International Fuel Gas Code" and replacing it
with "Uniform Plumbing Code as adopted by KMC."
301.7 Electrical.
Amend by deleting the reference "ICC Electrical Code" and replacing it with
"Electrical Code as adopted by KMC."
301.8 Plumbing connections.
Amend by deleting the reference "International Plumbing Code" and replacing it
with "Uniform Plumbing Code as adopted by the KMC."
303.3 Prohibited locations.
Amend by deleting the phrase "of the International Energy Conservation Code"
from the second sentence of Exception 3.
304.9 Clearances to combustible construction.
Amend to read:
304.9 Clearances to combustible construction. Heat -producing equipment
and appliances must be installed to maintain the required clearances to combustible
New Text Underhned•,[DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 14 of 21
construction as specified in the listing and manufacturer's instructions. These
clearances may be reduced only in accordance with Section 308 of the I.M.C. Certain
unlisted, heat -producing equipment shall be allowed if the equipment is installed in a
manner so as to maintain the clearances to combustible construction specified in
Table 304.8 of this Code. Clearances to combustibles must include considerations as
door swing, drawer pull, overhead proiections or shelving and window swing, shutters,
coverings, and drapes. Devices such as doorstops or limits, closers, drapery ties, or
guards, may not be used to provide the required clearances.
Amend to add Table 304.8 to read:
Table 304.8
New Text Underlined; [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 15 of 21
STANDARD INSTALLATION CLEARANCES, IN INCHES FOR CERTAIN UNLISTED HEAT -
PRODUCING APPLIANCES
New Text Underlined; [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 16 of 21
Appliances Fuel Above Top From Top From Front ' From Backs From Sides 6
of Casing and Sides
or Appliance of Warm -air
Bonnet or
Plenum
Furnaces -
Floor
For mount- Solid
182
182 48
18
18
ing on wm-
bustible
floors.
Automatic
36
12
12
12
Oil or comb.
Gas -oil
Boom Hastera3
Circulating Oil or
36
24
12
12
type. Solid
Radiant or Oil or
36
36
36
36
Other type. Solid
Fireplace stove Solid
484
54
484
484
Incinerators
Domestic
types
36,
48
36
36
Commercial -
Type
Low Heat
Appliances
Unit Heaters All fuels
18
48
18
18
Floor
mounted
any size.
Other low- All fuels
18
18 48
18
18
beat in.
duatrial
appliances.
Floor
mounted
or suspended.
Commercial
Industrial -
Type
Medium Heat
Appliances
Incinerators
48
96
36
36
All sizes.
Footnotes:
(1) The minimum dimension shall be that necessary for servicing the appliance, including access for cleaning and
normal care, tube removal, and similar items.
(2) The dimension may be six inches (152mm) for an automatically stoker -fired forced -warm -air furnace equipped
with 250 degree Fahrenheit limit control and with barometric draft control operated by draft intensity and
permanently set to limit draft to a maximum intensity of 0.13 -inch water gauge (32Pa).
(3) Approved appliances must be installed on non-combustible floors and may be installed on protected
combustible floors. Heating appliances approved for installation on protected combustible flooring shall be so
constructed that flame and hot gases do not come in contact with the appliance base. Protection for combustible
floors shall consist of four inch (102mm) hollow masonry covered with sheet metal at least 0.021 inch (0.5 -ax) thick
(NO. 24 manufacturer's standard gauge). Masonry must be permanently fastened in place in an approved manner
with the ends unsealed and joints matched so as to provide free circulation of air through the masonry Floor
protection shall extend 12 inches (305mm) at the sides and rear of the appliance, except that at least 18 inches
(459mm) shall be required on the appliance -opening side or sides measured horizontally from the edges of the
opening.
Ordinance No. 2663-2012
Page 17 of 21
312.1 Load Calculations.
Amend the third sentence by deleting the phrase "using the design parameters
specified in Chapter 3 of the International Energy Conservation Code."
403.3 Outdoor Airflow Rate.
Amend to read: Ventilation systems must be designed to have the capacity to
supply the minimum outdoor airflow rate required in Table 403.3 based on the
occupancy of the space and the occupant load or other parameter as stated herein, or
in accordance with the American Society of Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE) Standard 62 2010 Edition.
514.1 General.
Amend by deleting the second sentence and replacing it with a new second
sentence to read: Energy recovery ventilation systems must be installed according to
the manufacturer's instructions and specifications.
804.1 Direct Vent Termination.
Amend by adding a second sentence to read: Combustion vents for Direct Vent
Chambers are at least 3 foot high or provide snowdrift prevention.
907.1 General.
698 may not be acceptable as an alternative to UL 791.
908.5 Water supply.
Amend by deleting the reference "International Plumbing Code" and replacing it
with "Uniform Plumbing Code as adopted by KMC."
928 Unvented Room Heaters.
Amend by adding a new section 928 Unvented Room Heaters to read:
928.1 General. Unvented room heaters shall be tested in accordance with
American National Standards Institute (ANSI) Z 21.11.2 and may be installed in
accordance with the conditions of the listing and the manufacturer's
installation instructions.
928.2 Prohibited use. One or more unvented room heaters may not be used as
the sole source of comfort heating in a dwelling unit.
New Text Underlined: [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 18 of 21
928.3 Input rating. Unvented room heaters may not have an input rating in
excess of 40.000 Btu/h (11.7 kW).
combustion air from any of the following rooms or spaces:
1.
Sleeping rooms.
2.
Bathrooms.
3.
Toilet rooms.
4.
Storage closets.
5.
Surgical rooms.
Exceptions:
rating does not exceed 6,000 Btu per hour (1.76 kW) and the bathroom is not a
confined space.
2. A single wall -mounted unvented room heater equipped with an oxygen
depletion safety shutoff system and installed in a bedroom provided that the
input rating does not exceed 10,000 Btu per hour (2.93 kW) and the bedroom is
not a confined space.
928.5 Room or space volume. The aggregate input rating of all unvented
appliances installed in a room or space may not exceed 20 Btu/h per cubic foot
of volume of such room or space. Where the room or space in which the
equipment is installed is directly connected to another room or space by a
doorway, archway or other opening of comparable size that cannot be closed,
the volume of such adiacent room or space may be permitted to be included in
the calculations.
928.6 Oxygen -depletion safety system. Unvented room heaters will be
equipped with an oxygen -depletion -sensitive safety shutoff system. The system
shall shut off the gas supply to the main and pilot burners when the oxygen in
the surrounding atmosphere is depleted to the percent concentration specified
by the manufacturer, but not lower than 18 percent. The system will not
incorporate field adiustment means capable of changing the set point at which
the system acts to shut off the gas supply to room heater.
928.7 Unvented log heaters. An unvented log heater may not be installed in a
factory -built fireplace unless the fireplace system has been specifically tested,
New Text Underlined; [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 19 of 21
listed and labeled for such use in accordance with Underwriters Laboratories
UL 127.
CHAPTER 10 BOILERS, WATER HEATERS, AND PRESSURE VESSELS.
references occur in this Chapter 10.
1001.1 Scope.
Amend to read:
This chapter governs the installation, alteration and repair of boilers, water
heaters and pressure vessels not subiect to the provisions of the State Department of
Labor under AS 18.60.180 through 18.60.395.
1011 Tests.
Delete this section.
1101.4 Water connection.
Amend by deleting the reference "International Plumbing Code" and replacing it
with "Uniform Plumbing Code as adopted by KMC."
1201.1, 1206.2. and 1206.3
references occur in these sections.
1204.1 Insulation characteristics.
Amend the first sentence by deleting the phrase "shall conform to the
requirements of the International Energy Conservation Code."
1204.2 Required thickness.
Amend by deleting the phrase "to the thickness required by the International
Energy Conservation Code."
CHAPTER 14 SOLAR SYSTEMS
Amend by deleting the body of the chapter and inserting a new Section 1401 to
read: "General. Solar energy equipment and -appliances must be installed in
compliance with the Solar Energy Code as adopted by KMC.
New Text Underlined; [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 20 of 21
CHAPTER 15 REFERENCED STANDARDS.
Amend by changing the referenced NFPA Standards to the latest published
edition to read:
NFPA
4.20.020 Building Official.
The Building Official of this City shall have the powers, duties, and functions
prescribed for the "Code Official" by the International Mechanical Code adopted by
KMC 4.20.010, provided the powers, duties and functions may be performed by
authorized representatives of the Building Official and under his or her supervision
and control.
4.20.030 Fee schedule.
Section 106.5.2 of the International Mechanical Code adopted by this chapter is
amended to read:
If a building permit is issued, these fees shall be considered as paid as a part of
such permit fee. If no such building permit is issued, the fee shall be computed
according to [TABLE 1-A AT KMC 4.05.030(B)] the current City of Kenai Schedule of
Rates, Charges and Fees adopted by the Kenai City Council
Section 3. Severability: If any part or provision of this ordinance or application
thereof to any person or circumstances is adjudged invalid by any court of competent
jurisdiction, such judgment shall be confined in its operation to the part, provision, or
application directly involved in all controversy in which this judgment shall have been
rendered, and shall not affect or impair the validity of the remainder of this title or
application thereof to other persons or circumstances. The City Council hereby
declares that it would have enacted the remainder of this ordinance even without such
part, provision, or application.
New Text Underlined [DELETED TEXT BRACKETED]
Ordinance No. 2663-2012
Page 21 of 21
Section 4. Effective Date: Pursuant to KMC 1.15.070(f), this ordinance shall take
effect one month after adoption.
PASSED BY THE COUNCIL OF THE CITY OF KENAI, ALASKA, this 2nd day of
January, 2013.
PAT PO TER, MAYOR
ATTEST:
QWA7i-�u
S dr Modigho CMC
Ci erk
Introduced: December 19, 2012
Adopted: January 2, 2013
Effective: February 2, 2013
New Text Underlined; [DELETED TEXT BRACKETED]
M
""Viliaye with a Past, City with a Future
210 Fidalgo Avenue, Kenai, Alaska 99611-7794 boftd
Telephone: 907-283-75351 Fax: 907-283-3014
www.ci.kenai.ak.us V I I I
1992
Memorandum
�n To: City Council
- Through: Rick Koch, City Manager
From: Larry Floyd, Building Official
Date: December 11, 2012
Re: 2009 International Mechanical Code Adoption
The City of Kenai has historically adopted the latest edition of the International
Mechanical Code as the standard for mechanical systems design, construction and
maintenance in the City. The City has a deferral agreement with the State of Alaska which
requires the City of Kenai to adopt and enforce code standards no less stringent than those
enforced by the State. The State of Alaska adopted the 2009 International Mechanical Code
in November of this year.
I therefore recommend the adoption of the 2009 International Mechanical Code as
amended by the State of Alaska in order to comply with our deferral agreement and to
consistently enforce the code standards in effect throughout the State.