HomeMy WebLinkAboutOrdinance No. 3333-2023KENAI CITY OF KENAI ORDINANCE NO. 3333-2023 Sponsored by: Administration AN ORDINANCE AMENDING KENAI MUNICIPAL CODE 8.05.010 - ADOPTION OF FIRE PREVENTION STANDARDS, AND REPEALING AND REPLACING KENAI MUNICIPAL CODE 8.05.030 - LOCAL AMENDMENTS TO THE 2009 INTERNATIONAL FIRE CODE, TO ADOPT THE 2021 INTERNATIONAL FIRE CODE WITH LOCAL AMENDMENTS. WHEREAS, the City previously adopted the International Fire Code, 2009 Edition of the International Code Council, including the appendices with local amendments; and, WHEREAS, the State of Alaska has already adopted the updated International Fire Code 2021 Edition in October 2022, with local amendments; and, WHEREAS, the Administration accordingly recommend adoption of the 2021 Edition of the International Fire Code as adopted by the State of Alaska, with certain amendments; and, WHEREAS, it is in the best interest of the City to adopt the 2021 Edition of the International Fire Code and the updated standards therein as adopted by the State of Alaska, and amended for the City, in order to protect the health, safety, and welfare of its citizens. NOW, THEREFORE, BE IT ORDAINED BY THE COUNCIL OF THE CITY OF KENAI, ALASKA, AS FOLLOWS: Section 1. Amendment of Section 8.05.010 of Kenai Municipal Code: That Kenai Municipal Code, Section 8.05.010.Adoption of fire prevention standards, is hereby amended as follows: 8.06.010 Adoption of [F]Fire [P]Prevention [S]Standards. (a) There is hereby adopted for the purpose of regulating all occupancies and buildings to safeguard life and property from the hazards of fire and explosion arising from the storage, handling, and use of hazardous substances, materials, and devices, and from other conditions hazardous to life, that certain code known as the `International Fire Code," (IFC) Chapters 1-12, 20-40, 50-67 and 80 [THROUGH 47] and Appendices B through [G, ]l, K• L• and [J]N (20[09] 21 Edition) as adopted by the State of Alaska pursuant to 13 AAC 50.025 [AND THAT CERTAIN CODE KNOWN AS THE NATIONAL FIRE CODE OF FIFTEEN (15) VOLUMES (2009 EDITION) AS REFERENCED BY CHAPTER 45 OF THE IFC, ]except for such portions as are hereafter deleted, modified, or amended; and the same are hereby adopted and incorporated as fully as if set out verbatim herein. (b) The above codes are available for inspection and use by the public in the Public Safety Building in an office designated by the Fire Chief. Section 2. Repeal and Reenactment of Section 8.05.030 of Kenai Municipal Code: That Kenai Municipal Code, Section 8.05.030. Local amendments to the 2009 International Fire Code, is hereby Repealed and Reenacted as follows: New Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 2 of 23 [8.05.030 LOCAL AMENDMENTS TO THE 2009 INTERNATIONAL FIRE CODE. CHAPTERS 1 THROUGH 47 AND APPENDICES B THROUGH G, I, AND J OF THE INTERNATIONAL FIRE CODE, 2009 EDITION (IFC), AND THE NATIONAL FIRE CODE OF FIFTEEN (15) VOLUMES (2009 EDITION) ARE ADOPTED BY REFERENCE WITH THE FOLLOWING REVISIONS: DELETE THE FOLLOWING SUBSECTIONS: 308.4.1, 315.1, 601.2, 901.3, 1101.3, 1201.2, 1301.2, 1501.2, 1601.2, 1701.2, 1801.5, 1901.2, 2001.2, 2101.2, 2201.2, 2301.2, 2403.4, 2501.2, 2601.2, 2701.5, 2801.2, 2901.3, 3001.2, 3101.2, 3201.2, 3301.2, 3401.4, 3501.2, 3601.2, 3701.2, 3801.2, 3901.2, 4001.2, 4101.2, 4201.2, 4301.2 AND 4401.2. AMEND BY DELETING ALL REFERENCES TO THE "ICC ELECTRICAL CODE" AND REPLACING THEM WITH "ELECTRICAL CODE AS ADOPTED BY KMC." AMEND BY DELETING ALL REFERENCES TO THE "NFPA 70" AND REPLACING THEM WITH "ELECTRICAL CODE AS ADOPTED BY KMC." AMEND BY DELETING ALL REFERENCES TO THE "INTERNATIONAL FUEL GAS CODE" AND THE "INTERNATIONAL PLUMBING CODE" AND BY REPLACING THEM WITH "PLUMBING CODE AS ADOPTED BY KMC." 108 BOARD OF APPEALS. DELETE THE ENTIRE SECTION. REFER TO KMC CHAPTER 4.40. 109.3 VIOLATION PENALTIES. DELETE THE ENTIRE SECTION. REFER TO KMC CHAPTER 4.40. 111.4 FAILURE TO COMPLY. DELETE AND REPLACE WITH: ANY PERSON WHO SHALL CONTINUE ANY WORK AFTER HAVING BEEN SERVED WITH A STOP WORK ORDER, EXCEPT SUCH WORK AS THAT PERSON IS DIRECTED TO PERFORM TO REMOVE A VIOLATION OR UNSAFE CONDITION, SHALL BE LIABLE TO A FINE OF NOT MORE THAN $500.00 DOLLARS. EACH AND EVERY DAY SHALL CONSTITUTE A SEPARATE VIOLATION. 202 GENERAL DEFINITIONS. DELETE OCCUPANCY CLASSIFICATION, [B] EDUCATIONAL GROUP E, AND REPLACE WITH: [B] EDUCATIONAL GROUP E THE USE OF A BUILDING OR STRUCTURE, OR PORTION OF THE BUILDING OR STRUCTURE, FOR EDUCATION, SUPERVISION, OR PERSONAL CARE SERVICES FOR MORE THAN FIVE CHILDREN WHO ARE OLDER THAN TWO AND ONE-HALF YEARS OF AGE, INCLUDING CHILDREN RELATED TO THE STAFF SHALL BE CLASSIFIED AS A GROUP E OCCUPANCY. ADD THE FOLLOWING EXCEPTION: EXCEPTION FAMILY CHILD CARE HOMES (GROUP R-3) OPERATING BETWEEN THE HOURS OF 6:00 A.M. AND 10:00 P.M. MAY ACCOMMODATE A TOTAL OF 12 CHILDREN OF ANY AGE WITHOUT CONFORMING TO THE REQUIREMENTS OF A GROUP E OCCUPANCY EXCEPT FOR: (1) SMOKE DETECTORS AND ALARMS AS DESCRIBED IN SECTION 907.2.10; (2) CARBON MONOXIDE DETECTORS AND ALARMS AS SPECIFIED IN THE INTERNATIONAL BUILDING CODE SECTION 425; (3) MEANS OF EGRESS REQUIREMENTS OF SECTION 1003, INCLUDING EMERGENCY ESCAPE AND RESCUE OPENINGS, AS REQUIRED BY SECTION 1025, IN NAPPING OR SLEEPING ROOMS; AND (4) PORTABLE FIRE EXTINGUISHER REQUIREMENTS AS DESCRIBED IN SECTION 906. AMEND OCCUPANCY CLASSIFICATION, [B] INSTITUTIONAL GROUP 1-1, BY ADDING A PARAGRAPH BETWEEN THE FIRST AND SECOND PARAGRAPHS OF THE DEFINITION TO READ: New Text Undedined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 3 of 23 A FACILITY IN THIS OCCUPANCY CLASSIFICATION THAT HAS OCCUPANTS WHO NEED PHYSICAL ASSISTANCE TO RESPOND IN EMERGENCY SITUATIONS MUST COMPLY WITH THE INTERNATIONAL BUILDING CODE, SECTION 405. FURTHER AMEND OCCUPANCY CLASSIFICATION, [B] INSTITUTIONAL GROUP I-1, BY AMENDING THE FIRST SENTENCE OF THE LAST PARAGRAPH TO READ: A FACILITY SUCH AS ONE DESCRIBED ABOVE WITH FIVE OR FEWER PERSONS, INCLUDING PERSONS RELATED TO THE STAFF, SHALL BE CLASSIFIED AS GROUP R-3. AMEND OCCUPANCY CLASSIFICATION, [B] INSTITUTIONAL GROUP I, [B] GROUP I-2, BY ADDING A SECOND AND THIRD PARAGRAPH TO READ: A FACILITY SUCH AS ONE DESCRIBED ABOVE, WITH FIVE OR FEWER PERSONS INCLUDING PERSONS RELATED TO THE STAFF, SHALL BE CLASSIFIED AS GROUP R-3. A CHILD CARE FACILITY THAT PROVIDES CARE ON A 24-HOUR BASIS TO MORE THAN FIVE CHILDREN WHO ARE TWO AND ONE-HALF YEARS OF AGE OR LESS, INCLUDING CHILDREN RELATED TO THE STAFF SHALL BE CLASSIFIED AS GROUP 1-2. AMEND OCCUPANCY CLASSIFICATION, [B] INSTITUTIONAL GROUP I, [B] GROUP I-4, DAY CARE FACILITIES, BY REVISING THE SECOND SENTENCE TO READ: A FACILITY WITHIN THIS OCCUPANCY CLASSIFICATION WITH FIVE OR FEWER PERSONS, INCLUDING PERSONS RELATED TO THE STAFF, SHALL BE CLASSIFIED AS A GROUP R-3. AMEND OCCUPANCY CLASSIFICATION, RESIDENTIAL GROUP R, R-4, BY ADDING A PARAGRAPH BETWEEN THE FIRST AND SECOND PARAGRAPHS TO READ: FACILITIES WITHIN THIS OCCUPANCY CLASSIFICATION THAT HAVE OCCUPANTS NEEDING PHYSICAL ASSISTANCE TO RESPOND IN EMERGENCY SITUATIONS MUST COMPLY WITH THE INTERNATIONAL FIRE CODE SECTION 405.11. 307.2 PERMIT REQUIRED. DELETE AND REPLACE WITH: APPROVAL THE FIRE CHIEF OF A REGISTERED DEPARTMENT HAVING JURISDICTION, MAY ALLOW A FIRE FOR RECOGNIZED SILVICULTURAL OR RANGE OR WILDLIFE MANAGEMENT PRACTICES, PREVENTION, OR CONTROL OF DISEASE OR PESTS, OR A BONFIRE. APPLICATION, AS REQUIRED BY THE CHIEF OF THAT REGISTERED FIRE DEPARTMENT, MUST BE PRESENTED BY THE OWNER OF THE LAND UPON WHICH THE FIRE IS TO BE KINDLED BEFORE KINDLING SUCH FIRE. 308.3 OPEN FLAME. DELETE AND REPLACE WITH: OPEN FLAME THE USE OF OPEN FLAME IN CONNECTION WITH A PUBLIC MEETING OR GATHERING FOR THE PURPOSES OF DELIBERATION, WORSHIP, ENTERTAINMENT, AMUSEMENT, INSTRUCTION, EDUCATION, RECREATION, AWAITING TRANSPORTATION, OR SIMILAR PURPOSES IN ASSEMBLY OR EDUCATIONAL OCCUPANCIES MUST BE DONE IN CONSULTATION WITH THE REGISTERED FIRE DEPARTMENT HAVING JURISDICTION. 401.3.4 FALSEALARM CHARGES. ADD A NEW SUBSECTION 401.3.4 TO READ: 401.3.4 FALSE ALARM CHARGES New Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 4 of 23 EXCEPT AS OTHERWISE PROVIDED HEREIN, THE OWNER OF A BUILDING CONTAINING A FIRE PROTECTION, FIRE ALARM, OR OTHER TYPES OF EMERGENCY NOTIFICATION SYSTEMS, SHALL PAY A CHARGE IN ACCORDANCE WITH THIS SECTION FOR EACH AND EVERY FALSE ALARM TO WHICH THE FIRE DEPARTMENT RESPONDS. EXCEPTIONS: 1. NO CHARGE FOR THE FIRST TWO FALSE ALARMS WITHIN A CALENDAR YEAR. 2. EACH FALSE ALARM IN EXCESS OF TWO DURING A CALENDAR YEAR WILL BE CHARGED A RESPONSE FEE OF $200.00. THE CITY SHALL BILL THE OWNER FOR FALSE ALARMS AT THE END OF EVERY SIX MONTHS. ALL FALSE ALARM CHARGES SHALL BE DEPOSITED INTO THE CITY'S GENERAL FUND. AS USED BY THE SECTION, "FALSE ALARM" MEANS AN ALARM SIGNAL GENERATED BY A PRIVATELY OWNED FIRE OR EMERGENCY ALARM SYSTEM REPORTING AN ALARM FOR WHICH NO FIRE OR EMERGENCY ACTUALLY EXISTS; IT INCLUDES SYSTEM MALFUNCTIONS, FAULTY OPERATION OF DETECTORS, AND FALSE ALARMS NOT CLASSIFIED ABOVE. IT DOES NOT INCLUDE THOSE INCIDENTS WHERE THE DETECTOR OR SYSTEM OPERATED AS DESIGNED SUCH AS, BUT NOT LIMITED TO, A SMOKE DETECTOR SOUNDING FROM SOMEONE SMOKING UNDER THE DETECTOR OR A MANUAL PULL STATION BEING PULLED. 405.10 FALSE ALARMS. ADD A NEW SUBSECTION 405.10 TO READ: 405.10 FALSE ALARMS FALSE ALARMS MAY NOT COUNT AS A FIRE DRILL FOR THE PURPOSE OF SECTION 405 EMERGENCY EVACUATION DRILLS. ADD A NEW SUBSECTION 405.11 TO READ: 405.11 EMERGENCY EVACUATION DRILLS 405.11 OCCUPANTS NEEDING PHYSICAL ASSISTANCE 406.11.1 APPLICABILITY THE PROVISIONS OF THIS SECTION APPLY TO ALL GROUPS 1-1 AND R-4 OCCUPANCIES WHERE THE OCCUPANTS NEED PHYSICAL ASSISTANCE FROM STAFF OR OTHERS TO RESPOND TO EMERGENCIES. 405.11.2 DEFINITIONS IN THIS SECTION: "EVACUATION CAPABILITY" MEANS THE ABILITY OF OCCUPANTS, RESIDENTS, AND STAFF AS A GROUP EITHER TO EVACUATE A BUILDING OR TO RELOCATE FROM THE POINT OF OCCUPANCY TO A POINT OF SAFETY; "POINT OF SAFETY" MEANS A LOCATION THAT: (A) IS EXTERIOR TO AND AWAY FROM A BUILDING; OR (B) IS WITHIN A BUILDING OF ANY TYPE CONSTRUCTION PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM AND THAT IS EITHER: (1) WITHIN AN EXIT ENCLOSURE MEETING THE REQUIREMENTS OF I.B.C. SECTION 1020; OR (2) WITHIN ANOTHER PORTION OF THE BUILDING THAT IS SEPARATED BY SMOKE PARTITIONS MEETING THE REQUIREMENTS OF I.B.C. SECTION 710, WITH NOT LESS THAN A ONE-HALF HOUR FIRE RESISTANCE RATING, AND THE PORTION OF THE BUILDING HAS ACCESS TO A MEANS OF ESCAPE OR EXIT THAT CONFORMS TO THE REQUIREMENTS OF THIS CODE AND DOES NOT REQUIRE RETURN TO THE AREA OF THE FIRE. 405.11.3 FIRE DRILLS AND EVACUATION CAPABILITY DETERMINATION New Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 5 of 23 THE INITIAL DETERMINATION OF EVACUATION CAPABILITY WILL BE DETERMINED BY A FIRE DRILL CONDUCTED BY A FIRE CODE OFFICIAL OR BY AN EMPLOYEE OF THE DEPARTMENT OF HEALTH AND SOCIAL SERVICES RESPONSIBLE FOR LICENSING THE FACILITY. CHANGES TO THE EVACUATION CAPABILITY WILL BE MADE BY A FIRE CODE OFFICIAL, BASED ON A RECORD OF FIRE DRILLS CONDUCTED BY THE FACILITY STAFF. THE DRILLS WILL BE CONDUCTED SIX TIMES A YEAR ON A BIMONTHLY BASIS, WITH AT LEAST TWO DRILLS CONDUCTED DURING THE NIGHT WHEN RESIDENTS ARE SLEEPING. RECORDS MUST INDICATE THE TIME TAKEN TO REACH A POINT OF SAFETY, DATE AND TIME OF THE DRILL, LOCATION OF SIMULATED FIRE ORIGIN, ESCAPE PATHS USED, AND COMMENTS RELATING TO RESIDENTS WHO RESISTED OR FAILED TO PARTICIPATE IN THE DRILLS. 405.11.4 EVACUATION CAPABILITY AND FIRE PROTECTION REQUIREMENTS FIRE PROTECTION REQUIREMENTS OF A FACILITY UNDER THIS SECTION ARE AS FOLLOWS: 405.11.4.1 PROMPT EVACUATION CAPABILITY EVACUATION CAPABILITY OF THREE MINUTES OR LESS INDICATES PROMPT EVACUATION CAPABILITY. IN FACILITIES MAINTAINING PROMPT EVACUATION CAPABILITY, THE REQUIREMENTS OF THE CODE FOR GROUPS 1-1 OR R-4 OCCUPANCIES MUST BE FOLLOWED. 405.11.4.2 SLOW EVACUATION CAPABILITY EVACUATION CAPABILITY OF MORE THAN THREE BUT LESS THAN 14 MINUTES INDICATES SLOW EVACUATION CAPABILITY. IN FACILITIES MAINTAINING SLOW EVACUATION CAPABILITY, THE FACILITY MUST BE PROTECTED BY: (A) AN AUTOMATIC SMOKE DETECTION SYSTEM, USING ADDRESSABLE SMOKE DETECTORS, DESIGNED AND INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE AND N.F.P.A. 72; AND (B) AN AUTOMATIC SPRINKLER SYSTEM, WITH QUICK -RESPONSE OR RESIDENTIAL SPRINKLERS, INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.2 N.F. P.A. 13R (SPRINKLER SYSTEMS). 406.11.4.3IMPRACTICAL EVACUATION CAPABILITY EVACUATION CAPABILITY OF 14 MINUTES OR MORE INDICATES IMPRACTICAL EVACUATION CAPABILITY. IN FACILITIES MAINTAINING IMPRACTICAL EVACUATION CAPABILITY, THE FACILITY MUST BE PROTECTED BY: (A) THE PROTECTIONS FOR A FACILITY WITH SLOW EVACUATION CAPABILITY UNDER SECTION 405.11.4.2; (B) ONE-HALF HOUR FIRE -RESISTIVE CONSTRUCTION THROUGHOUT THE FACILITY; AND (C) DIRECT EGRESS FROM SLEEPING ROOMS FOR OCCUPANTS NEEDING EVACUATION ASSISTANCE EITHER: (1) TO THE EXTERIOR AT GRADE LEVEL, TO AN EXTERIOR PORCH OR LANDING VIA A 3 FOOT 6 INCH WIDE DOOR; OR (11) IF THE SLEEPING ROOMS ARE SEPARATED FROM THE REST OF THE BUILDING BY SMOKE PARTITIONS INSTALLED IN ACCORDANCE WITH I.B.C. SECTION 710, BY EGRESS WINDOWS CONFORMING TO THE PROVISIONS OF SECTION 1029. 407.1 GENERAL. DELETE AND REPLACE WITH: GENERAL. THE PROVISIONS OF SECTIONS 407.2 THROUGH 407.7 SHALL BE APPLICABLE, IN THE DISCRETION OF THE CHIEF OF THE REGISTERED FIRE DEPARTMENT THAT HAS JURISDICTION, WHERE HAZARDOUS MATERIALS ARE LOCATED ON THE PREMISES. 408.3 GROUP E AND/ OCCUPANCIES AND GROUP R-2 COLLEGE AND UNIVERSITY BUILDINGS. AMEND BY ADDING A NEW SUBSECTION 408.3.5 TO READ: 408.3.6 FALSE ALARMS FALSE ALARMS MAY NOT BE COUNTED AS A FIRE DRILL FOR THE PURPOSES OF THIS SECTION. 503.1.1 BUILDINGSAND FACILITIES. AMEND AS FOLLOWS: BUILDINGS AND FACILITIES New Tex[ Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 6 of 23 THE FIRE CHIEF OF THE REGISTERED DEPARTMENT HAVING JURISDICTION MAY REQUIRE APPROVED FIRE APPARATUS ROADWAYS FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING CONSTRUCTED OR MOVED INTO OR WITHIN THE JURISDICTION. THE FIRE APPARATUS ACCESS ROADWAY MUST BE REQUIRED TO COMPLY WITH THE REQUIREMENTS OF THIS SECTION AS DETERMINED BY THE CHIEF OF THAT JURISDICTION AND BE REQUIRED TO EXTEND WITHIN 150 FEET (45,720 MM) OF ALL PORTIONS OF THE FACILITY OR BUILDING OR ANY PORTION OF THE EXTERIOR WALL OF THE FIRST STORY OF THE FACILITY OR BUILDING AS MEASURED BY AN APPROVED ROUTE AROUND THE EXTERIOR OF THE BUILDING OR FACILITY. AMEND FURTHER BY REPLACING THE FIRST SENTENCE OF THE LISTED EXCEPTIONS TO READ: THE CHIEF (OR THEIR DESIGNEE) OF THE REGISTERED FIRE DEPARTMENT HAVING JURISDICTION MAY INCREASE OR DECREASE THE DIMENSION OF 150 FEET (45,720 MM) WHERE: 505.1 ADDRESS NUMBERS. AMEND THE FIRST SENTENCE AND INSERT A NEW SECOND SENTENCE TO READ: ALL NEW AND EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED ADDRESS NUMBERS, BUILDING NUMBERS, OR OTHER APPROVED BUILDING IDENTIFICATION CLEARLY VISIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY, OR ON THE STREET OR ROAD IF THE BUILDING IDENTIFICATION IS NOT VISIBLE FROM THE STREET OR ROAD. IDENTIFICATION MUST BE A MINIMUM OF FOUR INCHES IN HEIGHT AND A CONTRASTING COLOR. ON ALL NEW CONSTRUCTION THE ABOVE IDENTIFICATION SHALL BE LOCATED ON THE UPPER LEFT CORNER OF THE BUILDING AS VIEWED FROM THE STREET. 506.1 WHERE REQUIRED. AMEND BY DELETING THE PHRASE "IN AN APPROVED LOCATION'S IN THE FIRST SENTENCE AND REPLACING IT WITH "FULLY VISIBLE AND RECOGNIZABLE FROM THE MAIN OR FRONT ENTRANCE TO THE BUILDING." 507.5.4 OBSTRUCTIONS. AMEND BY ADDING THE PHRASE "DEPOSITING OF SNOW WITHIN THREE (3) FEET OF A HYDRANT'S TO THE END OF THE FIRST SENTENCE. 703.2.3 DOOR OPERATION. ADD A NEW SUBSECTION 703.2.3.1 TO READ: 703.2.3.1 OPERATION FIRE ASSEMBLIES MAY NOT BE OBSTRUCTED OR OTHERWISE IMPAIRED FROM THEIR PROPER OPERATION AT ANY TIME. WHEN TWO OR MORE SELF -CLOSING FIRE ASSEMBLIES WITHIN A BUILDING HAVE BEEN DOCUMENTED AS HAVING BEEN OBSTRUCTED OR IMPAIRED DURING THREE OR MORE CONSECUTIVE INSPECTIONS, THE FIRE CODE OFFICIAL MAY ORDER THE INSTALLATION OF AUTOMATIC -CLOSING DEVICES MEETING THE REQUIREMENTS OF SECTION 714.4.7.2 OF THE I.B.C. 901.4 INSTALLATION OF FIRE PROTECTION SYSTEMS. AMEND BY ADDING AN EXCEPTION AT THE END OF THIS SUBSECTION TO READ: EXCEPTION BUILDINGS TEMPORARILY CLOSED DUE TO SEASONAL OPERATIONS MAY HAVE THEIR FIRE SYSTEMS DEACTIVATED UNDER THE FOLLOWING CONDITIONS: 1. BUILDING IS UNOCCUPIED. 2. BUILDING IS PROPERLY SECURED. 3. ALL UTILITIES ARE DISCONNECTED AND DRAINED. 4. THE FIRE SYSTEMS ARE CERTIFIED AS OPERATIONAL BEFORE THE BUILDING IS REOCCUPIED. 5. A 24-HOUR A DAY FIRE WATCH AS DEFINED IN SECTION 202 IS PROVIDED DURING THE INTERIM BETWEEN WHEN UTILITIES ARE REACTIVATED AND THE FIRE SYSTEMS ARE CERTIFIED AS OPERATIONAL. New Text Underlined; [DELETED TEXT BRACKETED] a _J Ordinance No. 3333-2023 Page 7 of 23 6. THE FIRE DEPARTMENT MUST BE NOTIFIED OF SUCH CLOSURE. 7. A LETTER FROM THE INSURANCE CARRIER OR, OWNER IF SELF -INSURED, INDICATING KNOWLEDGE OF THE CLOSURE IS PROVIDED TO THE FIRE DEPARTMENT. 901.4.5 MARKING OF FIRE PROTECTION EQUIPMENT. ADD A NEW SUBSECTION 901.4.5 TO READ: 901.4.5 MARKING OF FIRE PROTECTION EQUIPMENT. FIRE DEPARTMENT CONNECTION DEVICES FOR BUILDING SPRINKLER SYSTEMS IN NEW AND EXISTING BUILDINGS SHALL BE IDENTIFIED BY THE INSTALLATION OF SIGNS INSTALLED ABOVE THE DEVICE IN AN UNOBSTRUCTED LOCATION AT APPROXIMATELY 7 FEET ABOVE GRADE. FDC SIGNS SHALL BE A MINIMUM OF 8 X 12 INCHES IN SIZE AND HIGHLY VISIBLE WITH CONTRASTING COLORS. 901.5 INSTALLATION ACCEPTANCE TESTING. AMEND BY ADDING A THIRD SENTENCE TO THE END OF THE PARAGRAPH TO READ: ALL RESULTS OF SUCH TEST MUST BE FORWARDED TO THE KENAI FIRE MARSHAL WITHIN 30 DAYS. 901.6INSPECTION, TESTING AND MAINTENANCE. AMEND BY ADDING A NEW SECOND PARAGRAPH TO READ: SUPERSEDING OTHER CODE OR STANDARD REQUIREMENTS, FIRE PROTECTION SYSTEMS AND FIRE EXTINGUISHERS MUST BE INSPECTED, TESTED, AND SERVICED AS FOLLOWS: 1. ANNUALLY EXCEPT STANDPIPE SYSTEMS MUST BE INSPECTED, TESTED, AND SERVICED EVERY FIVE YEARS. 2. AFTER ANY USE OR ACTIVATION. 3. ANYTIME DAMAGE IS FOUND. 4. AFTER REPAIR OR ALTERATION. 5. WHEN REQUIRED BY THE CHIEF. 6. AFTER SEASONAL SHUTDOWN. 901.6.2.2 REPORTS. ADD A NEW SUBSECTION 901.6.2.2 TO READ: 901.6.2.2 REPORTS A COPY OF ALL SERVICE REPORTS SHALL BE SENT TO THE KENAI FIRE MARSHAL WITHIN 30 DAYS. EACH SYSTEM SHALL BE TAGGED BY THE INSPECTION AGENCY, INDICATING THE DATE OF SERVICE AND WHETHER OR NOT THE SYSTEM IS IN CONFORMANCE WITH THE ASSOCIATED STANDARDS. 901.7 SYSTEMS OUT OF SERVICE. DELETE THE FIRST SENTENCE AND REPLACE WITH: WHERE A REQUIRED FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN EIGHT HOURS IN A TWENTY-FOUR HOUR PERIOD, AN IMPAIRMENT PLAN WILL BE SUBMITTED TO THE FIRE DEPARTMENT AND THE FIRE CODE OFFICIAL IMMEDIATELY AND, WHERE REQUIRED BY THE FIRE CODE OFFICIAL, THE BUILDING SHALL EITHER BE EVACUATED OR AN APPROVED FIRE WATCH SHALL BE PROVIDED FOR ALL OCCUPANTS LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE PROTECTION SYSTEM HAS BEEN RETURNED TO SERVICE. 901.10 DAMAGE PROTECTION. ADD A NEW SUBSECTION 901.10 TO READ: 901.10 DAMAGE PROTECTION NEW TEXT Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 8 of 23 WHEN EXPOSED TO PROBABLE VEHICULAR DAMAGE DUE TO PROXIMITY TO ALLEYS, DRIVEWAYS OR PARKING AREAS, STANDPIPES, POST INDICATOR VALVES AND SPRINKLER SYSTEM OR STANDPIPE SYSTEM, CONNECTIONS SHALL BE PROTECTED IN AN APPROVED MANNER. 903.2.3 GROUP E. DELETE AND REPLACE WITH: GROUP E AN AUTOMATIC SPRINKLER SYSTEM MUST BE PROVIDED THROUGHOUT ALL GROUP E OCCUPANCIES. AN AUTOMATIC SPRINKLER SYSTEM SHALL ALSO BE PROVIDED FOR EVERY PORTION OF EDUCATIONAL BUILDINGS BELOW THE LEVEL OF EXIT DISCHARGE. THE USE OF FIRE WALLS DOES NOT ESTABLISH A SEPARATE BUILDING FOR PURPOSES OF THIS SECTION. DAY CARE USES THAT ARE LICENSED TO CARE FOR MORE THAN 5 PERSONS BETWEEN THE HOURS OF 10:00 P.M. AND 6:00 A.M. SHALL BE EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM DESIGNED AND INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.3. THIS INCLUDES CHILDREN RELATED TO THE STAFF. EXCEPTION: 1. BUILDINGS WITH E OCCUPANCIES HAVING AN OCCUPANT LOAD OF 49 OR LESS. 903.2.8 GROUP R. DELETE AND REPLACE WITH: GROUP R AN AUTOMATIC SPRINKLER SYSTEM MUST BE INSTALLED IN GROUP R OCCUPANCIES AS REQUIRED IN SECTIONS 903.2.8.1 THROUGH 903.2.8.2. EXCEPTION: ALL R-3S AND BED AND BREAKFAST OCCUPANCIES WITH FIVE RENTED SLEEPING ROOMS OR LESS DO NOT REQUIRE AN AUTOMATIC SUPPRESSION SYSTEM. 903.2.8.1 GROUP R-1. ADD A NEW SUBSECTION 903.2.8.1 TO READ: 903.2.8.1 GROUP R-1 HEALTH CLINICS WITH TRANSIENT QUARTERS MAY UTILIZE A 13D SPRINKLER SYSTEM THROUGHOUT THE BUILDING; A FIRE BARRIER CAN BE UTILIZED TO SEPARATE THE BUILDING AND UTILIZE A 13R. 903.2.8.2 GROUP R-2. ADD NEW SUBSECTION 903.2.8.2 TO READ: 903.2.8.2 GROUP R-2. AN AUTOMATIC SPRINKLER SYSTEM OR A RESIDENTIAL SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.2 SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R-2 FIRE AREA THAT ARE MORE THAN TWO STORIES IN HEIGHT, INCLUDING BASEMENT, OR HAVE MORE THAN 4 DWELLING UNITS OR 16 SLEEPING ROOMS. 903.3.1.1.2 ELEVATOR HOISTWAYS AND MACHINE ROOMS. ADD A NEW SUBSECTION 903.3.1.1.2 TO READ: 903.3.1.1.2 ELEVATOR HOISTWAYS AND MACHINE ROOMS WHEN THE PROVISIONS OF THIS CODE REQUIRE THE INSTALLATION OF AUTOMATIC SPRINKLER SYSTEMS, THE INSTALLATION IN ELEVATOR HOISTWAYS AND MACHINE ROOMS MUST OCCUR AS DESCRIBED IN N.F.P.A. 13, (ELEVATOR HOISTWAYS AND MACHINE ROOMS) AND ADOPTED BY REFERENCE AND THE AMERICAN SOCIETY FOR MECHANICAL ENGINEERS (A.S.M.E.) A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS AND ADOPTED BY REFERENCE. THE FIRE SPRINKLER HEAD FOR THE TOP OF ELEVATOR SHAFTS MAY HAVE A GLOBE VALVE INSTALLED SO THE SINGLE HEAD CAN BE TURNED OFF IN AN EMERGENCY. THE GLOBE VALVE MUST BE MARKED AND SEALED OR LOCKED IN THE OPEN POSITION. New Tex[ Underlined; [DELETED TEXT BRACKETED] r-, Ordinance No. 3333-2023 Page 9 of 23 EXCEPTION: SPRINKLERS ARE NOT REQUIRED IN AN ELEVATOR MACHINE ROOM WHERE THE MACHINE ROOM IS: (1) SEPARATED FROM THE REMAINDER OF THE BUILDING AS DESCRIBED IN I.B.C. SECTION 3006.4; (2) SMOKE DETECTION IS PROVIDED IN ACCORDANCE WITH N.F.P.A.72 AND ADOPTED BY REFERENCE; (3) NOTIFICATION OF ALARM ACTIVATION IS RECEIVED AT A CONSTANTLY MONITORED LOCATION; AND (4) FIRE EXTINGUISHER IS PROVIDED IN THE ELEVATOR MACHINE ROOM. 903.3.1.1.3 INSPECTORS TEST VALVE. ADD A NEW SUBSECTION 903.3.1.1.3 TO READ: 903.3.1.1.3 INSPECTORS TEST VALVE A TEST VALVE WILL BE INSTALLED AT THE FAR END OF THE REMOTE AREA IN WET SYSTEMS TO EQUAL THE REQUIRED FLOW OF ONE SPRINKLER HEAD. IN LOCATIONS THAT USE FLOOR CONTROL VALVES THE INSPECTOR TEST VALVE MAY BE CO -LOCATED. APPROPRIATE DRAINAGE SHALL BE PROVIDED. 903.6.3 ALTERATIONS AND ADDITIONS TO E OCCUPANCIES. ADD NEW SUBSECTION 903.6.3 TO READ: 903.6.3 ALTERATIONS AND ADDITIONS TO E OCCUPANCIES AN APPROVED AUTOMATIC FIRE SUPPRESSION SYSTEM MUST BE INSTALLED IN E OCCUPANCIES IN ACCORDANCE WITH SECTION 903.2.3 WHENEVER ALTERATIONS OR ADDITIONS ARE MADE TO AN EXISTING STRUCTURE CONTAINING E OCCUPANCY. 906.1 WHERE REQUIRED. AMEND BY DELETING THE EXCEPTION FROM NUMBER 1. 907.1.2 CONSTRUCTION DOCUMENTS. AMEND BY ADDING NEW ITEMS TO THE LIST TO READ: 14. SYSTEM RISER DIAGRAM. 15. FIRE SYSTEM DESIGNER STAMP, SIGNATURE AND DATE. 907.2.1 GROUP A. DELETE THE EXCEPTION AND REPLACE WITH: EXCEPTION: A MANUAL FIRE ALARM SYSTEM SHALL BE INSTALLED IN GROUP A-2 OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE. 907.2.2 GROUP B. AMEND BY DELETING THE EXCEPTION. 907.2.3 GROUP E. AMEND BY ADDING A SECOND PARAGRAPH TO READ: ROOMS USED FOR SLEEPING OR NAPPING PURPOSES WITHIN A DAY CARE USE OF GROUP E OCCUPANCIES MUST BE PROVIDED WITH SMOKE DETECTORS THAT COMPLY WITH SECTION 907.2.11.2 AND BY DELETING EXCEPTION 3. 907.2.4 GROUP F. AMEND BY DELETING THE EXCEPTION. 907.2.6.1 GROUP I-1. AMEND BY DELETING EXCEPTION 1. 907.2.7GROUP M. AMEND BY DELETING EXCEPTION 2. 907.2.8.1 MANUAL FIRE ALARM SYSTEM. AMEND BY DELETING EXCEPTION 2. New Text Underlined; [DELETEDTEXT BRACKETED] Ordinance No. 3333-2023 Page 10 of 23 907.2.9.1 MANUAL FIRE ALARM SYSTEM. AMEND BY DELETING EXCEPTION 2. 907.2.10.1 MANUAL FIRE ALARM SYSTEM. AMEND BY DELETING EXCEPTION 2. 907.2.11 SINGLE- AND MULTI -STATION SMOKE ALARMS. AMEND BY ADDING A SECOND PARAGRAPH TO READ: WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A PERMIT ARE MADE TO AN EXISTING GROUP R OCCUPANCY, SMOKE ALARMS MUST BE INSTALLED AS DESCRIBED IN SECTION 907.2.11. 907.8 ACCEPTANCE TEST AND COMPLETION. AMEND BY ADDING A SECOND PARAGRAPH TO READ: A KENAI CODE OFFICIAL MUST WITNESS THE ACCEPTANCE TEST, AND A COPY OF THE ACCEPTANCE TEST CERTIFICATE MUST BE FORWARDED TO THE KENAI FIRE MARSHAL BY THE FIRM CONDUCTING THE TEST WITHIN 30 DAYS OF THE COMPLETION OF THE INSTALLATION. 908.7 CARBON MONOXIDE DETECTORS. ADD A NEW SUBSECTION 908.7 TO READ: 908.7 CARBON MONOXIDE DETECTORS CARBON MONOXIDE DETECTORS SHALL BE INSTALLED ON EACH FLOOR LEVEL OF GROUP 1-1, 1-2 AND R OCCUPANCIES. WHERE THERE ARE SLEEPING ROOMS ON A FLOOR, THE DETECTOR SHALL BE PLACED OUTSIDE THE SLEEPING ROOMS. THE ALARM SHALL BE CLEARLY AUDIBLE IN ALL BEDROOMS OVER BACKGROUND NOISE LEVELS WITH ALL INTERVENING DOORS CLOSED. ALL CARBON MONOXIDE DETECTORS SHALL BE LISTED AND INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE. EXCEPTION: CARBON MONOXIDE DETECTORS AND ALARMS ARE NOT REQUIRED IN DWELLING UNITS AND STRUCTURES THAT HAVE NO COMBUSTION APPLIANCES, ATTACHED GARAGES, OTHER VEHICLE PARKING WITHIN 25 FEET OF ANY DIRECT OPENING, OR HAVE ONLY DIRECT VENT COMBUSTION APPLIANCES. IN NEW CONSTRUCTION, ALL CARBON MONOXIDE DETECTORS AND ALARMS LOCATED WITHIN A SINGLE DWELLING UNIT SHALL BE INTERCONNECTED IN SUCH A MANNER THAT ACTUATION OF ONE ALARM SHALL ACTIVATE ALL OF THE ALARMS WITHIN THE INDIVIDUAL DWELLING UNIT. IN NEW CONSTRUCTION, CARBON MONOXIDE DETECTORS AND ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING IF THE WIRING IS SERVED FROM A COMMERCIAL SOURCE, AND SHALL BE EQUIPPED WITH A BATTERY BACKUP. WIRING SHALL BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH OTHER THAN WHAT IS REQUIRED FOR OVERCURRENT PROTECTION. IN EXISTING CONSTRUCTION, CARBON MONOXIDE DETECTORS AND ALARMS MAY BE POWERED BY BATTERY OR A CORD -AND -PLUG WITH BATTERY BACKUP CARBON MONOXIDE DETECTORS SHALL HAVE AN ALARM AND BE INSTALLED AND MAINTAINED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. THE LANDLORD SHALL PROVIDE SMOKE AND CARBON MONOXIDE DETECTION DEVICES. IT IS THE RESPONSIBILITY OF THE TENANT TO MAINTAIN THE DEVICES. 908.8 POWER SOURCE. ADD A NEW SUBSECTION 908.8 TO READ: 908.8 POWER SOURCE IN NEW CONSTRUCTION, THE REQUIRED CARBON MONOXIDE DETECTORS SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING SYSTEM, AND WHEN PRIMARY POWER IS INTERRUPTED, SHALL RECEIVE POWER FROM A BATTERY. WIRING SHALL BE PERMANENTAND WITHOUTA DISCONNECTING SWITCH OTHER THAN THOSE REQUIRED FOR OVER CURRENT PROTECTION. CARBON MONOXIDE DETECTORS SHALL BE PERMITTED TO BE ELECTRICAL OUTLET TYPE WITH BATTERY BACK UP WHEN INSTALLED IN EXISTING BUILDINGS THAT UNDERGO ALTERATIONS, REPAIRS, OR ADDITIONS THAT DO NOT RESULT IN THE REMOVAL OF THE INTERIOR WALL OR CEILING FINISHES EXPOSING THE STRUCTURE. New Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 11 of 23 908.8.1 INTERCONNECTION. ADD A NEW SUBSECTION 908.8.1 TO READ: 908.8.1 INTERCONNECTION IN NEW CONSTRUCTION, ALL CARBON MONOXIDE DETECTORS AND ALARMS LOCATED WITHIN A SINGLE DWELLING UNIT SHALL BE INTERCONNECTED IN SUCH A MANNER THAT ACTUATION OF ONE ALARM SHALL ACTIVATE ALL OF THE ALARMS WITHIN THE INDIVIDUAL DWELLING UNIT. 909.18 ACCEPTANCE TESTS. AMEND BY ADDING A NEW SENTENCE TO READ: A COPY OF THE ACCEPTANCE TEST CERTIFICATE MUST BE FORWARDED TO THE FIRE MARSHAL HAVING AUTHORITY BY THE FIRM CONDUCTING THE TEST WITHIN 30 DAYS OF THE COMPLETION OF THE INSTALLATION. 910.1 GENERAL. AMEND BY DELETING EXCEPTION 2. 912.2.1 VISIBLE LOCATION. DELETE AND REPLACE WITH: THE FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED FULLY VISIBLE AND RECOGNIZABLE FROM THE MAIN OR FRONT ENTRANCE TO THE BUILDING. 1007.3 STAIRWAYS. AMEND BY DELETING EXCEPTIONS 1 THROUGH 7. 1009.1 STAIRWAYS. AMEND BY ADDING A NEW EXCEPTION TO READ: 5. STAIRS OR LADDERS USED ONLY TO ATTEND EQUIPMENT ARE EXEMPT FROM THE REQUIREMENTS OF THIS SECTION. 1009.6.2 OUTDOOR CONDITIONS. AMEND BY ADDING THE PHRASE "SNOW OR ICE" AFTER THE WORD "WATER." 1010.7.2 OUTDOOR CONDITIONS. AMEND BY ADDING THE PHRASE "SNOW OR ICE" AFTER THE WORD "WATER." TABLE 1018.1 CORRIDOR FIRE -RESISTANCE RATING. AMEND BY ADDING A NOTE (D) TO READ: (D) R-2 OCCUPANCIES SHALL BE PERMITTED TO HAVE A ONE -HOUR RATED CORRIDOR. FURTHER, AMEND BY ADDING A REFERENCE TO THE NEW NOTE (D) AT R UNDER THE "OCCUPANCY" COLUMN ON THE LEFT OF THE TABLE AND ALSO NEXT TO "NOT PERMITTED" IN THE 'WITHOUT SPRINKLER SYSTEM" COLUMN. 1019.1 GENERAL. AMEND BY ADDING A NEW SENTENCE AT THE END OF THE SECTION TO READ: EXTERIOR EXIT BALCONIES SHALL BE DESIGNED TO MINIMIZE ACCUMULATION OF SNOW OR ICE THAT IMPEDES THE MEANS OF EGRESS. 1021.2 SINGLE EXITS. AMEND BY ADDING A SECOND PARAGRAPH TO READ: BASEMENTS OR THE FIRST LEVEL BELOW THE FIRST STORY IN ALL OCCUPANCIES, EXCEPT GROUP R-3, USED EXCLUSIVELY FOR THE SERVICE OF THE BUILDING MAY HAVE ACCESS TO ONLY ONE EXIT. ANY OTHER USE OF THE BASEMENT OR FIRST LEVEL BELOW THE FIRST STORY MUST HAVE AT LEAST TWO EXITS ARRANGED IN ACCORDANCE WITH SECTION 1015.2. FOR PURPOSES OF THIS EXCEPTION, STORAGE ROOMS, LAUNDRY ROOMS, MAINTENANCE OFFICES, AND SIMILAR USES MAY NOT BE CONSIDERED AS PROVIDING SERVICE TO THE BUILDING. 1029.1 GENERAL. AMEND BY DELETING EXCEPTIONS 1, 2, 3, 4, AND 7. 1102.1 DEFINITIONS. AMEND BY DELETING THE PHRASE "WITH AN OVERALL LENGTH GREATER THAN 39 FEET (11,887 MM) AND AN OVERALL EXTERIOR FUSELAGE WIDTH GREATER THAN 6.6 FEET (2,012 MM)" IN THE FIRST SENTENCE OF THE DEFINITION OF "AIRPORT." NOW Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 12 of 23 1103.5 DISPENSING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. DELETE THE LAST SENTENCE AND REPLACE WITH: AIRCRAFT MOTOR VEHICLE FUEL -DISPENSING STATIONS SHALL BE IN ACCORDANCE WITH CHAPTER 22, AND N.F.P.A. 407. 1105.8 REPORTING USE. DELETE SUBSECTION 1105.8. 1106.3 CONSTRUCTION OF AIRCRAFT -FUELING VEHICLES AND ACCESSORIES. AMEND BY ADDING AN EXCEPTION AT THE END OF THIS SUBSECTION TO READ: EXCEPTION A VEHICLE OR TRAILER TANK WITH A CAPACITY OF 250 GALLONS OR LESS MAY BE USED FOR NONCOMMERCIAL REFUELING OF PRIVATE NONCOMMERCIAL AIRCRAFT IF THE FOLLOWING REQUIREMENTS ARE MET: 1. THE TANK IS PLACARDED WITH NO SMOKING SIGNS, TYPE OF FUEL CONTAINED IN THE TANK AND THE TANK CAPACITY; 2. THE TANK AND ALL APPURTENANCES USED IN THE FUELING OPERATION ARE LISTED AND APPROVED FOR THE SPECIFIC PURPOSES; AND 3. ELECTRICAL BONDING IS PROVIDED AS REQUIRED UNDER SECTION 1106.3.7. 2206.2.3 ABOVE GROUND TANKS LOCATED OUTSIDE, ABOVE GRADE. AMEND BY ADDING A NEW ITEM 5 TO READ: 5. APPROVED ABOVE GROUND ATMOSPHERIC TANKS MAYBE USED WITHOUT SPECIAL ENCLOSURE OR FIRE RATING IF THE FOLLOWING CRITERIA ARE MET: A. TANKS MUST BE LOCATED AS REQUIRED FOR "OTHER TANKS" BY TABLE 2206.2.3; AND B. TANKS MUST BE ENCLOSED BY A SIX-FOOT HIGH INDUSTRIAL TYPE CHAIN LINK FENCE WITH A MINIMUM OF TWO ACCESS GATES LOCATED AT OPPOSITE SIDES OF THE ENCLOSURE. EACH GATE MUST BE AT LEAST 36 INCHES WIDE. THERE MUST BE A MINIMUM WORKING DISTANCE OF FIVE FEET BETWEEN THE TANK AND THE FENCE. 2206.7.7.1 LEAK DETECTION. AMEND BY ADDING AN EXCEPTION TO READ: EXCEPTION A LEAK DETECTION DEVICE IS NOT REQUIRED IF THE UNDERGROUND PIPING IS AN EXTRA -HEAVY STEEL WALL WITH ALL WELDED JOINTS, DIELECTRIC COATING, AND CATHODIC PROTECTION. 2211.2.3 DRAINAGE AND DISPOSAL OF LIQUIDS AND OIL -SOAKED WASTE. AMEND BY ADDING A SENTENCE AT THE END OF THE FIRST PARAGRAPH TO READ: WHERE OIL SEPARATORS OR TRAPS ARE PROVIDED, NEITHER THE OIL NOR WATER PHASE MAY DRAIN TO A SEPTIC SYSTEM, DRY WELL OR OTHER MEANS OF UNDERGROUND DISCHARGE. TABLE 2306.2 GENERAL FIRE PROTECTION AND LIFE SAFETY REQUIREMENTS. AMEND THE TABLE BY CHANGING THE SPRINKLER REQUIREMENT FOR THE AREA OF "501-2,500" (SQUARE FEET) IN THE THIRD COLUMN FROM THE LEFT SIDE OF THE TABLE TITLED "AUTOMATIC FIRE EXTINGUISHING SYSTEM' FROM "NOT REQUIRED" TO "YES." 2701.6 FACILITY CLOSURE. DELETE AND REPLACE WITH: DOCUMENTATION New Text Underlined; [DELETED TEXT BRACKETED] L_j Ordinance No. 3333-2023 Page 13 of 23 THE FIRE CHIEF OF THE REGISTERED FIRE DEPARTMENT HAVING JURISDICTION MAY REQUIRE THE DOCUMENTATION OF THE CLOSURE PLANS FOR THE TERMINATION OF THE STORAGE, USE, OR HANDLING OF HAZARDOUS MATERIALS AT LEAST 30 DAYS BEFORE THE TERMINATION. THE FIRE CHIEF IS AUTHORIZED TO REQUIRE THAT THE DOCUMENTATION INCLUDE AN APPROVED FACILITY CLOSURE PLAN IN ACCORDANCE WITH SECTION 2701.6.3. THE FIRE CHIEF MAY REQUIRE THE SUBMISSION OF THE HAZARDOUS MATERIALS MANAGEMENT PLAN AND HAZARDOUS MATERIALS INVENTORY STATEMENT INDICATED IN SECTIONS 2701.5.1 AND 2701.5.2. CHAPTER 33 EXPLOSIVES AND FIREWORKS. DELETE THIS CHAPTER. REFER TO KMC CHAPTER 8.20, FIREWORKS CONTROL. 3404.3.5.1 BASEMENT STORAGE. DELETE THIS SUBSECTION. 3501.3 PLAN REVIEW. ADD A NEW SUBSECTION 3501.3 TO READ: 3501.3 PLAN REVIEW. WHERE A SINGLE CONTAINER IS OVER 500-GALLON (1,892.7 L) WATER CAPACITY OR THE AGGREGATE CAPACITY OF CONTAINERS IS OVER 500-GALLON (1,892.7 L) WATER CAPACITY, THE INSTALLER SHALL SUBMIT PLANS FOR REVIEW BY THE FIRE MARSHAL BEFORE INSTALLATION. CHAPTER 47 REFERENCED STANDARDS CHANGE THE REFERENCED NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) STANDARDS FROM THE PUBLICATION DATE LISTED TO THE FOLLOWING EDITIONS: 10-10 PORTABLE FIRE EXTINGUISHERS 11-10 LOW-, MEDIUM -AND HIGH -EXPANSION FOAM 12-11 CARBON DIOXIDE EXTINGUISHING SYSTEMS 12A-09 HALON 1301 FIRE EXTINGUISHING SYSTEMS 13-10 INSTALLATION OF SPRINKLER SYSTEMS TABLE 901.6.1, 906.2, 906.3, TABLE 906.3(1), TABLE 906.3(2), 906.3.2, 906.3.4, 2106.3, 1101.1 904.7, 3404.2.9.2.2 TABLE 901.6.1. 904.8. 904.11 TABLE 901.6.1, 904.9 903.3.1.1, 903.3.2, 903.3.5.1.1, 903.3.5.2,904.11, 905.3.4, 907.7.3, 2301.1, 2304.2, TABLE 2306.2, 2306.9, 2307.2,2307.2.1, 2308.2.2, 2308.2.2.1, 2308.4, 2310.1, 2501.1, 2804.1, 2806.5.7, 3404.3.3.9, TABLE 3404.3.6.3(7), 3404.3.7.5.1, 3404.3.8.4 1313-10 INSTALLATION OF SPRINKLER SYSTEMS 903.3.1.3, 903.3.5.1.1 IN ONE- AND TWO-FAMILY DWELLINGS AND MANUFACTURED HOMES 13R-10 INSTALLATION OF SPRINKLER SYSTEMS 903.3.1.2, 903.3.5.1.1, 903.3.5.1.2, 903.4 IN RESIDENTIAL OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN HEIGHT NOW Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 14 of 23 14-10 INSTALLATION of STANDPIPE AND HOSE 905.2, 905.3.4, 905.4.2, 905.6.2, 905.8 SYSTEMS 15-12 WATER SPRAY FIXED SYSTEMS FOR FIRE 3404.2.9.2.3 PROTECTION 16-11 INSTALLATION OF FOAM -WATER 904.7, 904.11 SPRINKLER AND FOAM -WATER SPRAY SYSTEMS 17-09 DRY CHEMICAL EXTINGUISHING SYSTEMS TABLE 901.6.1, 904.6, 904.11 17A-09 WET CHEMICAL EXTINGUISHING TABLE 901.6.1, 904.5, 904.11 SYSTEMS 20-10 INSTALLATION OF STATIONARY PUMPS 913.1, 913.2, 913.5.1 FOR FIRE PROTECTION 22-08 WATER TANKS FOR PRIVATE FIRE 507.2.2 PROTECTION 24-10 INSTALLATION OF PRIVATE FIRE SERVICE 507.2.1, 1909.5 MAINS AND THEIR APPURTENANCES 25-11 INSPECTION, TESTING AND 507.5.3, TABLE 901.6.1, 904.7.1, 912.6, 913.5, MAINTENANCE OF WATER -BASED FIRE 1101.1 PROTECTION SYSTEMS 30-12 FLAMMABLE AND COMBUSTIBLE LIQUIDS 3403.6.2, 3403.6.2.1, 3404.2.7, 3404.2.7.1, CODE 3404.2.7.2, 3404.2.7.3.6, 3404.2.7.4, 3404.2.7.6, 3404.2.7.7, 3404.2.7.8, 3404.2.7.9, 3404.2.9.3, 3404.2.9.4, 3404.2.9.6.1.1, 3404.2.9.6.1.2, 3404.2.9.6.1.3, 3404.2.9.6.1.4, 3404.2.9.6.1.5, 3404.2.9.6.2, 3404.2.9.7.4, 3404.2.10.2, 3404.2.11.4, 3404.2.11.5.2, 3404.2.12.1, 3404.3.1, 3404.3.6, TABLE 3404.3.6.3(1), TABLE 3404.3.6.3(2), TABLE 3404.3.6.3(3), 3404.3.7.2.3, 3404.3.8.4, 3406.8.3 30A-12 CODE FOR MOTOR FUEL -DISPENSING 2201.4, 2201.5, 2201.6, 2206.6.3, 2210.1 FACILITIES AND REPAIR GARAGES 30B-11 MANUFACTURE AND STORAGE OF 2801.1, 2803.1, 2804.1, TABLE 2804.3.1, AEROSOL PRODUCTS TABLE 2804.3.2, TABLE 2804.3.2.2, 2804.4.1, 2804.5.2, 2804.6, 2806.2.3, 2806.3.2, TABLE 2806.4, 2806.5.1, 2806.5.6, 2807.1 31-11 INSTALLATION OF OIL -BURNING 603.1.7, 603.3.1, 603.3.3 EQUIPMENT 32-11 DRY CLEANING PLANTS 1207.1, 1207.3 New Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 15 of 23 33-11 SPRAY APPLICATION USING FLAMMABLE 1504.3.2 OR COMBUSTIBLE MATERIALS 34-11 DIPPING AND COATING PROCESSES 1505.3, 1505.4.1.1 USING FLAMMABLE OR COMBUSTIBLE LIQUIDS 35-11 MANUFACTURE OF ORGANIC COATINGS 2001.3, 2005.4 40-11 STORAGE AND HANDLING OF CELLULOSE 306.2 NITRATE FILM 51-07 DESIGN AND INSTALLATION OF OXYGEN- 2601.5, 2607.1, 2609.1 FUEL GAS SYSTEMS FOR WELDING, CUTTING AND ALLIED PROCESSES 51A-12 ACETYLENE CYLINDER CHARGING 2608.1 PLANTS 52-10 VEHICULAR FUEL SYSTEM CODE 3001.1 55-10 STANDARD FOR THE STORAGE, USE AND 2209.2.1, 3201.1, 3501.1, 4001.1 HANDLING OF COMPRESSED GASES AND CRYOGENIC FLUIDS IN PORTABLE AND STATIONARY CONTAINERS CYLINDERS AND TANKS 58-11 LIQUEFIED PETROLEUM GAS CODE 603.4.2.1.1, 3801.1, 3803.1, 3803.2.1, 3803.2.1.2, 3803.2.1.7, 3803.2.2, 3804.1, 3804.3.1, 3804.4, 3806.2, 3806.3, 3807.2, 3808.1, 3808.2, 3809.11.2, 3811.3 59A-09 PRODUCTION, STORAGE AND HANDLING OF LIQUEFIED NATURAL GAS (LNG) 61-08 PREVENTION OF FIRES AND DUST EXPLOSIONS IN AGRICULTURAL AND FOOD PROCESSING FACILITIES 69-08 EXPLOSION PREVENTION SYSTEMS 70-11 NATIONAL ELECTRICAL CODE 3001.1, 3201.1 TABLE 1304.1 911.1, 911.3, TABLE 1304.1 603.1.3, 603.1.7, 603.5.2, 604.2.15.1, 605.3, 605.4, 605.9, 606.16, 904.3.1, 907.1, 909.11, 909.12.1, 909.16.3, 1106.3.4, 1204.2.3, TABLE 1304.1, 1404.7, 1503.2.1, 1503.2.1.1, 1503.2.1.4, 1503.2.5, 1504.9.4, 1604.5, 1703.2, 1803.7.1, 1803.7.2, 1803.7.3, 1903.4, 2004.1, 2205.4, 2208.8.1.2.4, 2209.2.3, 2211.3.1, 2211.8.1.2.4, 2403.12.6.1, 2404.15.7, 2606.4, 2703.7.3, 3003.7.6, 3003.8, 3003.16.11, 3003.16.14, 3203.6, 3203.7.2, 3403.1, TABLE 3403.1.1, 3403.1.3, 3404.2.8.12, 3404.2.8.17, 3406.2.8, 3503.1.5, 3503.1.5.1, 3507.1.10, 3606.5.5, 3606.5.6, 3704.2.2.8 New Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 16 of 23 72-10 NATIONAL FIRE ALARM CODE 80-10 FIRE DOORS AND OTHER OPENING PROTECTIVES 85-11 BOILER AND COMBUSTION SYSTEM HAZARDS CODE 86-11 OVENS AND FURNACES 99-12 HEALTH CARE FACILITIES 101-12 LIFE SAFETY CODE 105-10 INSTALLATION OF SMOKE DOOR ASSEMBLIES AND OTHER OPENING PROTECTIVES 110-10 EMERGENCY AND STANDBY POWER SYSTEMS 111-11 STORED ELECTRICAL ENERGY EMERGENCY AND STANDBY POWER SYSTEMS 120-10 COAL PREPARATION PLANTS 160-11 FLAME EFFECTS BEFORE AN AUDIENCE 170-09 STANDARD FOR FIRE SAFETY AND EMERGENCY SYMBOLS 211-10 CHIMNEYS, FIREPLACES, VENTS AND SOLID FUEL -BURNING APPLIANCES 241-09 SAFEGUARDING CONSTRUCTION, ALTERATION AND DEMOLITION OPERATIONS 253-11 STANDARD TEST FOR CRITICAL RADIANT FLUX OF FLOOR COVERING SYSTEMS USING A RADIANT HEAT ENERGY SOURCE 260-09 METHODS OF TESTS AND CLASSIFICATION SYSTEM FOR CIGARETTE IGNITION RESISTANCE OF COMPONENTS OF UPHOLSTERED FURNITURE 508.1.5, TABLE 901.6.1, 903.4.1, 904.3.5, 907.2, 907.2.6, 907.2.11, 907.2.13.2, 907.3, 907.4.3, 907.4.4, 907.6.2.1.2, 907.6.2.2, 907.7, 907.7.1, 907.7.2, 907.7.5, 907.8, 907.8.1, 907.8.2, 907.9, 907.9.2, 907.9.5, 001.1, A03.1.4 703.1.3, 1008.1.3.3 TABLE 1304.1 2101.1 3006.4 1028.6.2 703.1.2 604.1, 604.3, 604.4, 913.5.2, 913.5.3 604.1, 604.3, 604.4 TABLE 1304.1 308.3.2 1024.2.6.1 603.2 1401.1 804.3 805.1.1.1, 805.2.1.1, 805.3.1.1, 805.4.1.1 261-09 METHOD OF TEST FOR DETERMINING 805.2.1.1, 805.3.1.1, 805.4.1.1 RESISTANCE OF MOCK-UP UPHOLSTERED New Text Underlined; [DELETED TEXT BRACKETED] L' Ordinance No. 3333-2023 Page 17 of 23 FURNITURE MATERIAL ASSEMBLIES TO IGNITION BY SMOLDERING CIGARETTES 265-11 METHOD OF FIRE TESTS FOR 803.5.1, 803.5.1.1, 803.5.1.2, 805.4.1.1 EVALUATING ROOM FIRE GROWTH CONTRIBUTION OF TEXTILE WALL COVERINGS IN FULL HEIGHT PANELS AND WALLS 286-11 STANDARD METHOD OF FIRE TESTS FOR 803.1, 803.1.2, 803.1.2.1, 803.5.1 EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH 303-11 FIRE PROTECTION STANDARD FOR 905.3.7, 4503.5, 4503.6, 4504.2 MARINAS AND BOATYARDS 385-07 TANK VEHICLES FOR FLAMMABLE AND 3406.5.4.5, 3406.6, 3406.6.1 COMBUSTIBLE LIQUIDS 407-12 AIRCRAFT FUEL SERVICING 1106.2, 1106.3 409-11 AIRCRAFT HANGARS 914.8.2, TABLE 914.8.2, 914.8.2.1, 914.8.5 484-12 COMBUSTIBLE METALS TABLE 1304.1 495-10 EXPLOSIVE MATERIALS CODE 911.1, 911.4, 3301.1.1, 3301.1.5, 3302.1, 3304.2, 3304.6.2, 3304.6.3, 3304.7.1, 3305.1, 3306.1, 3306.5.2.1, 3306.5.2.3, 3307.1, 3307.9, 3307.11, 3307.15 498-10 SAFE HAVENS AND INTERCHANGE LOTS 3301.1.2 FOR VEHICLES TRANSPORTING EXPLOSIVES 505-11 POWERED INDUSTRIAL TRUCKS, 2703.7.3 INCLUDING TYPE DESIGNATIONS, AREAS OF USE, MAINTENANCE AND OPERATION 654-06 PREVENTION OF FIRE AND DUST TABLE 1304.1 EXPLOSIONS FROM THE MANUFACTURING, PROCESSING AND HANDLING OF COMBUSTIBLE PARTICULATE SOLIDS 655-07 PREVENTION OF SULFUR FIRES AND TABLE 1304.1 EXPLOSIONS 664-12 PREVENTION OF FIRES AND EXPLOSIONS TABLE 1304.1, 1905.3 IN WOOD PROCESSING AND WOODWORKING FACILITIES 701-10 METHODS OF FIRE TESTS FOR FLAME- 806.2, 807.1, 807.1.2, 807.2, 807.4.2.2, PROPAGATION OF TEXTILES AND FILMS 1703.5, 2404.2 New Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 18 of 23 703-12 FIRE RETARDANT IMPREGNATED WOOD 803.4 AND FIRE RETARDANT COATINGS FOR BUILDING MATERIALS 704-12 IDENTIFICATION OF THE HAZARDS OF 606.7, 1802.1, 2404.2, 2703.2.2.1, MATERIALS FOR EMERGENCY RESPONSE 2703.2.2.2, 2703.5, 2703.10.2, 2705.1.10, 705.2.1.1, 2705.4.4, 3203.4.1, 3404.2.3.2, F101.1,F101.2 750-10 WATER MIST FIRE PROTECTION SYSTEMS TABLE 901.6.1 1122-08 MODEL ROCKETRY 1123-10 FIREWORKS DISPLAY 1124-06 MANUFACTURE, TRANSPORTATION, STORAGE AND RETAIL SALES OF FIREWORKS AND PYROTECHNIC ARTICLES 1125-12 MANUFACTURE OF MODEL ROCKET AND HIGH POWER ROCKET MOTORS 1126— USE OF PYROTECHNICS BEFORE A 116 PROXIMATE AUDIENCE 1127-08 HIGH POWER ROCKETRY 1142-12 WATER SUPPLY FOR SUBURBAN AND RURAL FIRE FIGHTING 2001-12 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS 3301.1.4 3302.1, 3304.2, 3308.1, 3308.2.2, 3308.5, 3308.6 3302.1, 3304.2, 3305.1, 3305.3, 3305.4, 3305.5 3301.1.4 3304.2, 3305.1, 3308.1, 3308.2.2, 3308.4, 3308.5 3301.1.4 B103.3 TABLE 901.6.1,904.10 APPENDIX OF THE I.F.C. AMEND THE APPENDIX BY ADDING A NEW APPENDIX K TO READ: APPENDIX K FIRE STATUS REPORTING K101 (SCOPE) ALL FIRE SERVICE COMPANIES PROVIDING SERVICES IN THE STATE OF ALASKA SHALL PROVIDE A LEGIBLE COPY OF ALL FIRE SYSTEM SERVICE REPORTS TO THE FIRE MARSHAL OFFICE AS ADOPTED AND AMENDED TO THE 2009 INTERNATIONAL FIRE CODE AS LISTED BELOW. EXEMPTION: INDUSTRIAL OCCUPANCIES WITH AN APPROVED FIRE SYSTEM PREVENTIVE MAINTENANCE PROGRAM. SEE BELOW FOR CONTACT INFORMATION. K102 (STATUS 1) SYSTEMS OUT OF SERVICE OR MAJOR DEFICIENCIES THE FIRE SERVICE COMPANY SHALL IMMEDIATELY CONTACT THE FIRE MARSHAL OFFICE, IF THE SYSTEM CANNOT BE RETURNED TO SERVICE. ON A WEEKEND OR AFTER HOURS, CONTACT THE FIRE MARSHAL OFFICE ON THE FIRST BUSINESS DAY. WRITTEN NOTIFICATION SHALL BE FAXED TO THE FIRE MARSHAL OFFICE WITHIN 24 HOURS. NOTIFICATION MAY BE MADE BY EMAIL. K102.1 CORRECTIVE ACTION TIME New Text Undedlned; [DELETED TEXT BRACKETED] r Ordinance No. 3333-2023 Page 19 of 23 STATUS 1 REPORTS SHALL BE REPAIRED IMMEDIATELY. K702.1.1 FOR EXAMPLE BUT NOT LIMITED TO K102.1.1.1 FIRE SPRINKLER OR WATER BASED SYSTEMS 1. NON -WORKING FLOW/PRESSURE SWITCHES. 2. DAMAGE TO FIRE DEPARTMENT CONNECTIONS. 3. NO WATER TO SYSTEM. 4. FROZEN OR OTHERWISE DAMAGED SYSTEM. K102.1.1.2 FIRE PUMPS 1. NON -WORKING FIRE PUMPS. 2. FIRE PUMP CONTROLS NOT WORK OR MALFUNCTIONING. K102.1.1.3 FIRE ALARM SYSTEMS (DETECTION AND ALARM) 1. NON -WORKING FIRE ALARM PANEL. 2. MALFUNCTIONING FIRE ALARM PANEL. 3. AUDIO AND VISUAL DEVICES NOT WORKING ENTIRE NAC LOOP. 4. DETECTION NOT WORKING ENTIRE DETECTION LOOP. 5. LOSS OF PROGRAMMING. K102.1.1.4 KITCHEN HOOD FIRE SYSTEMS 1. SYSTEM CYLINDER IS NOT CHARGED OR LEAKING. 2. APPLIANCE NOT PROPERLY COVERED DUE TO REARRANGEMENT OF APPLIANCES. 3. PLUGGED DISCHARGE NOZZLES. 4. AUTOMATIC DETECTION NOT FUNCTIONAL. 5. GAS OR ELECTRIC NOT SHUTTING DOWN. K102.1.1.5 CLEAN AGENT OR SPECIAL HAZARD SYSTEM 1. SYSTEM CYLINDER IS NOT CHARGED OR LEAKING. 2. RELEASING PANEL NOT FUNCTIONAL. K103 (STATUS 2) SYSTEMS K103 (STATUS 2) SYSTEMS THAT HAVE CRITICAL DEFICIENCY REPORTS SHALL BE PROVIDED TO THE FIRE MARSHAL OFFICE WITHIN 14 DAYS. K103.1 CORRECTIVE ACTION TIME STATUS 2 SYSTEMS SHALL BE REPAIRED WITHIN 14 DAYS. K103,1.1 FOR EXAMPLE (BUT NOT LIMITED TO): K103.1.1.1 FIRE SPRINKLER OR WATER BASED SYSTEM New Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 20 of 23 1. FIVE OR MORE PAINTED SPRINKLER HEADS IN A CONCENTRATED AREA OR MORE THAN 10 IN A FACILITY. 2. CHANGE OF USE THAT WILL AFFECT THE PERFORMANCE OF THE SPRINKLER SYSTEM. 3. LOW WATER PRESSURE. 4. ANY OTHER MAJOR PROBLEM THAT WILL AFFECT THE PERFORMANCE. 5. NO MONITORING ON REQUIRED SYSTEMS. K103.1.1.2 FIRE PUMPS 1. LOW FUEL. 2. PUMP PACKING LEAKING BEYOND SPECIFICATIONS. 3. FIRE PUMP ROOM BELOW 40 DEGREES. 4. FIRE PUMP NOT MEETING ITS RATED DISCHARGE PRESSURE OR GPM FLOW OVER A 10% DIFFERENCE. 5. ANY OTHER MAJOR PROBLEM THAT WILL AFFECT THE PERFORMANCE. K103.1.1.3 FIRE ALARM SYSTEMS (DETECTION AND ALARM) 1. BATTERIES OVERDUE FOR REPLACEMENT. 2. NO MONITORING ON REQUIRED SYSTEM. 3. AUDIO AND VISUAL DEVICES NOT WORKING — UP TO 3 DEVICES, OVER 3 DEVICES STATUS 1. 4. DETECTION NOT WORKING — UP TO 3 DEVICES, OVER 3 DEVICES STATUS 1. 5. ANY OTHER MAJOR PROBLEM THAT WILL AFFECT THE PERFORMANCE. K103.1.1.4 KITCHEN HOOD FIRE SYSTEMS 1. HOOD AND DUCTS WITH HEAVY GREASE BUILDUP. 2. ANY OTHER MAJOR PROBLEMS THAT WILL AFFECT THE PERFORMANCE. K104 (STATUS 3) MINOR DEFICIENCY REPORTS SHALL BE PROVIDED TO THE FIRE MARSHAL'S OFFICE WITHIN 30 DAYS. THESE DEFICIENCIES WILL NOT AFFECT THE PERFORMANCE OF THE SYSTEM. K104.1 CORRECTIVE ACTION TIME STATUS 3 SYSTEMS SHALL BE REPAIRED WITHIN 30 DAYS. K705 (STATUS 4) SYSTEM WITH NO DEFICIENCIES SHALL BE REPORTED TO THE FIRE MARSHALS OFFICE WITHIN 30 DAYS. K105.1 SYSTEM SERVICE REPORTS SHALL HAVE THE FOLLOWING INFORMATION ON THEM: 1. INSPECTION COMPANY NAME SHALL BE PRINTED ON ALL REPORTS WITH ADDRESS AND PHONE NUMBER. 2. INSPECTOR'S FIRST AND LAST NAME SHALL BE PRINTED WITH STATE OF ALASKA FIRE SYSTEMS PERMIT NUMBER. 3. INSPECTOR'S PHONE NUMBER: OFFICE AND CELL IF AVAILABLE. New Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 21 of 23 4. DEFICIENCIES SHALL BE TYPED OR LEGIBLY HAND WRITTEN AND SHALL BE PRINTED TEXT (NO CURSIVEILONG HAND HANDWRITING). REPORTS WILL BE WRITTEN WITH A MINIMUM LINE SPACING OF A 3/8 INCH PER LINE. 5. ALL REPORTS SHALL HAVE BUILDING NAME, OCCUPANCY INSPECTED, ANDADDRESS CLEARLY IDENTIFIED ON THE 1ST PAGE, AND ALL SUBSEQUENT PAGES SHALL HAVE THE BUILDING NAME AND DATE OF INSPECTION ON THE TOP OF THE PAGE. 6. ALL REPORTS SHALL HAVE THE BUILDING CONTACT PERSONS NAME WITH PHONE NUMBER ON THE FRONT PAGE. 7. ONLY WHITE AND YELLOW COPIES WILL BE ACCEPTED FOR REPORTS SUBMITTED. 8. DEFICIENCY WRITE UPS MUST INCLUDE THE CODE CITATION THAT IS IN VIOLATION AND A DESCRIPTION OF THE PROBLEM. ITEMS HAVING MINOR DEFICIENCIES SHALL BE MAILED WITHIN 30 DAYS TO: THE KENAI FIRE MARSHAL OFFICE 105 SOUTH WILLOW STREET KENAI, AK 99611--- 907-283-7666--- 907-283-8171 FAX SYSTEMS OUT OF SERVICE AND THOSE WITH MAJOR DEFICIENCIES SHALL HAVE A REPORT FAXED AND MAILED IMMEDIATELY WITHIN 1 DAY TO THE ADDRESS ABOVE.] 8.05.030 Local Amendments to the 2021 International Fire Code. Amend by deleting all references to the "ICC Electrical Code" and replacing them with "Electrical Code as adopted by KMC." Amend by deleting all references to the "NFPA 70" and replacing them with "Electrical Code as adopted by KMC." 111 Means of Appeals. Delete the entire section. Refer to KMC Chapter 4.40. 112.4 Violation Penalties. Delete the entire section. Refer to KMC Chapter 4.40 113.4 Failure to Comply. Delete and replace with: L_; 903.3.1.1 NFPA 13 Sorinkler Systems. Amend by adding a new subsection to read: New Text Underlined; [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 22 of 23 903.3.1.2.4 Elevator Hoist Ways and Machine Rooms must be marked and sealed or locked in the open position. Exception Sprinklers are not required in an elevator machine room where the machine room is: (1) Separated from the remainder of the building as described in Section 3006.4; (2) Smoke detection is provided in accordance with NFPA: (3) Notification of alarm activation is received at a constantly monitored location: and (4) Fire extinguisher is provided in the elevator machine room. 907 1 2 Fire Alarm Shop Drawings Amend by adding the following to the end of the paragraph to read as follows System riser diagrams and Fire system designer stamp signature, date. 907 2.2 Group B. Amend by deleting the exception. 907 2 7 Group M. Amend by deleting Exception 2. 907.2.8.1 Manual Fire Alarm System. Amend by deleting Exception 2. 907.2.9.1 Manual Fire Alarm System. Amend by deleting Exception 2. 915.1. Carbon Monoxide Detectors Add a new subsection 915.1.1.1 Carbon Monoxide Detectors,_ to read as follows: Carbon monoxide detectors shall be installed on each floor level of Groups 1-1, 1-2, 1-4 and R occupancies Where there are sleeping rooms on a floor, the detector shall be placed outside the sleeping rooms The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed All carbon monoxide detectors shall be listed and installed in accordance with the provisions of this code. 1009 1 Stairway Width Amend by adding exception to read 3 Ladders used only to attend equipment are exempt from the requirements of Section 1009. egress. Chapter 56 Section 5601 1 3 (Fireworks) of the IFC is revised with the exception remaining, to read: "The storage use and handling of fireworks is prohibited except as allowed in this section and KMC 8.20, Fireworks control. Section 3. Severability: That if any part or provision of this ordinance or application thereof to any person or circumstances is adjudged invalid by any court of competent jurisdiction, such judgment shall be confined in its operation to the part, provision, or application directly involved in all controversy in New Text Underlined. [DELETED TEXT BRACKETED] Ordinance No. 3333-2023 Page 23 of 23 which this judgment shall have been rendered, and shall not affect or impair the validity of the remainder of this title or application thereof to other persons or circumstances. The City Council hereby declares that it would have enacted the remainder of this ordinance even without such part, provision, or application. Section 4. Effective Date: That pursuant to KMC 1.15.070(D, this ordinance shall take effect 30 days after enactment. ENACTED BY THE COUNCIL OF THE CITY OF KENAI, ALASKA, THIS 1ST DAY OF FEBRUARY, 2023. ATTE Michelle . er, C, ity 6erk Brian Gabriel Sr., Mayor Introduced: Enacted: Effective: New Text Underlined; [DELETED TEXT BRACKETED] January 18, 2023 February 1, 2023 March 3, 2023 �8V KENAI City of Kenai 1 210 Fidalgo Ave, Kenai, AK 99611-7794 1907.283.7535 1 www.kenai.city MEMORANDUM TO: Mayor Gabriel and Council Members THROUGH: Terry Eubank, City Manager THROUGH: Scott Curtin, Director of Public Works FROM: Don Hendrickson, Building Official DATE: January 11, 2023 SUBJECT: Ordinance 3333-2023 Fire Code Adoption This memo requests Council's approval and support in the adoption of the newest edition of the International Fire Code. The State of Alaska this past fall formally adopted the 2021 edition, and it is our recommendation that it is in the best interest of the City to follow suit and adopt this edition as well. This code, similar to the Building Codes, are generally revised every three years, and Kenai is currently working from the 2009 edition respectively. Adoption of this code will improve coordination with Architects and Engineers who generally prefer to work with the newer codes. Generally 90+% of the code remain very similar from version to version, with typically certain sections seeing appropriate updates based on the latest standards and best practices. The Building Official and Fire Marshal have coordinated efforts on the local amendments appropriate for our area. Adoption of this code at this time will provide staff with the tools required to ensure construction projects and occupied facilities are meeting appropriate standards within City limits. The Department is working toward updating our permit packets and applications and with Council's approval the new codes and forms will be ready for the upcoming construction season. Council's support is respectfully requested.